Model H1301 Recovery and Recycling System
Installation, Operation and Maintenance Manual
Revision-L September, 2019
Page 90 of 105
VII. System Maintenance Procedures
P. Cooling System Controller Setting (continued)
3. Cooling System Temperature Controller Setup Parameters (continued)
To access the Setup Mode:
a. Press and hold the Function-key then press and hold with the UP arrow key within
30 seconds after power on: the controller will enter the Select Mode. Press the
Down Arrow-key so that the upper display indicates SEtP. Press the Function-key:
the lower line should display ULOC.
b. Use the UP arrow key to enter the number 20 into the upper display line then press
the Function-key. The controller should now enter the setup programming mode.
c. Use the Function-key to step through the menu items.
Setup Mode Factory Settings:
Prompt Setting
FilE 2.0
OFFS Adjust per the Calibration Procedure section-2
PPLJ Power Output Read Only
Pb_P 0
diFP .5
SPuL 80
SPLL -80
Ctl 8
APE diSA
PoEn diSA
_SPr diSA
rP OFF (upper display is blank)
SP -63
SLoc 20