1 Selection of language
VWDUW JXLGH
,I WKH VWDUW JXLGH LV OHIW RQ WKLV SDJH LW FORVHV
DXWRPDWLFDOO\ LQ
PLQ
Choose the language that you want the information to
be displayed in here.
Change language as follows:
1.
Turn the control knob until the language you require
is marked.
2.
Press the OK button.
3.
Turn the control knob until the arrow in the top left
corner (at the page number) has been marked.
4.
Press the OK button to access the next step in the
start guide.
2 Information
VWDUW JXLGH
:HOFRPH WR WKH VWDUW JXLGH IRU \RXU KHDW SXPS
$V ORQJ DV WKH VWDUW JXLGH LV DFWLYH QR IXQFWLRQ
LQ WKH KHDW SXPS ZLOO VWDUW DXWRPDWLFDOO\
7KH JXLGH ZLOO VKRZ XS ZLWK HDFK UHVWDUW RI WKH
KHDW SXPS XQWLO LW LV GHVHOHFWHG RQ WKH ODVW
SDJH
Information about the start guide for the heat pump is
shown here.
3 Setting "operating mode brine pump"
VWDUW JXLGH
LQWHUPLWWHQW
FRQWLQXRXV
GD\V FRQWLQXRXV
RSHUDWLQJ PRGH EULQH SXPS
op. mode
Setting range: intermittent, continuous, 10 days con-
tinuous
Default value: intermittent
Set the operating mode of the brine pump here.
intermittent: The brine pump starts 20 seconds before
and stops at the same time as the compressor.
continuous: Continuous operation.
10 days continuous: Continuous operation for 10 days.
Then the pump shifts to intermittent operation.
TIP
You can use “10 days continuous" at start-up
to obtain continuous circulation during a start-
up time in order to make it easier to bleed the
system.
29Chapter 6 | Commissioning and adjustingNIBE™ F1245