Technical specifications
60403024Model
Output data according to EN 14511
----kWHeating capacity (P
H
)
0/35
59.2239.9430.7223.00kWHeating capacity (P
H
)
13.728.906.924.94kWSupplied power (P
E
)
4.324.494.444.65-COP
0/45
56.1238.9029.7421.98kWHeating capacity (P
H
)
16.0210.618.345.96kWSupplied power (P
E
)
3.503.673.573.69-COP
10/35
78.3251.7140.0830.04kWHeating capacity (P
H
)
15.089.817.245.30kWSupplied power (P
E
)
5.195.275.535.67-COP
10/45
74.2150.7939.1629.28kWHeating capacity (P
H
)
17.6011.828.846.34kWSupplied power (P
E
)
4.224.304.434.62-COP
Output data according to EN 14825
67463528kWP
designh
, 35 °C / 55 °C
4.7 / 3.85.0 / 3.94.9 / 3.85.0 / 4.0-SCOP cold climate, 35 °C / 55 °C
4.6 / 3.74.8 / 3.84.7 / 3.64.8 / 3.8-SCOP average climate, 35 °C / 55 °C
Energy rating, average climate
A+++ / A++A+++ / A++A+++ / A++A+++ / A++-The product’s room heating efficiency class 35 °C / 55 °C
1
A+++ / A++A+++ / A++A+++ / A++A+++ / A++-The system’s room heating efficiency class 35 °C / 55 °C
2
Electrical data
400V 3N ~ 50Hz-Rated voltage
44.329.525.320.5A
rms
Max operating current, heat pump
3
19.913.111.18.4A
rms
Max operating current per compressor
50353025ARecommended fuse rating
53423029A
rms
Starting current
0.4---ohmMax permitted impedance at connection point
4
40 – 1,25035 – 7306 – 3606 – 360WTotal output, Brine pumps
3
5 – 1745 – 1745 – 1745 – 174WTotal output, HM pumps
IP 21-Enclosure class
Refrigerant circuit
R410AR407CR407CR407C-Type of refrigerant
2 x 1.72 x 1.72 x 2.02 x 2.0kgVolume
2,0881,7741,7741,774-GWP refrigerant
2 x 3.552 x 3.022 x 3.552 x 3.55tonCO
2
equivalent
4.2 (42 bar)3.2 (32 bar)3.2 (32 bar)3.2 (32 bar)MPaCut-out value pressostat HP
-0.7 (-7 bar)-0.7 (-7 bar)-0.7 (-7 bar)-0.7 (-7 bar)MPaDifference pressostat HP
0.2 (2 bar)0.08 (0.8 bar)0.08 (0.8 bar)0.08 (0.8 bar)MPaCut-out value pressostat LP
0.07 (0.7 bar)0.07 (0.7 bar)0.07 (0.7 bar)0.07 (0.7 bar)MPaDifference pressostat LP
0.2 (2.0 bar)0.08 (0.8 bar)0.08 (0.8 bar)0.08 (0.8 bar)MPaCut-out value, pressure transmitter LP
0.01 (0.1 bar)0.01 (0.1 bar)0.01 (0.1 bar)0.01 (0.1 bar)MPaDifference, pressure transmitter LP
Brine circuit
0.6 (6 bar)0.6 (6 bar)0.6 (6 bar)0.6 (6 bar)MPaMax system pressure brine
2.361.591.230.92l/sMin flow
3.102.091.621.18l/sNominal flow
78927592kPaMax external available press at nominal flow
5
see diagram°CMin/Max incoming Brine temp
-12-12-12-12°CMin. outgoing brine temp.
Heating medium circuit
0.6 (6 bar)0.6 (6 bar)0.6 (6 bar)0.6 (6 bar)MPaMax system pressure heating medium
0.920.640.500.37l/sMin flow
1.340.930.730.54l/sNominal flow
50707278kPaMax external avail. pressure at nominal flow
see diagram°CMin/max HM-temp
NIBE F1345Chapter 8 | Technical data46