Technical specifications
F2040-16F2040-12F2040-8Air-water heat pump
NominalNominalNominalOutd. temp: /
Supply temp.
Heating
7.03/1.45/4.855.21/1.09/4.783.86/0.83/4.657/35 °C (floor)
Output data according to EN14511 ΔT5K
9.33/2.38/3.926.91/1.79/3.865.11/1.36/3.762/35 °C (floor)
Specified/supplied power/COP (kW/kW/-)
12.12/4.33/2.808.98/3.26/2.756.64/2.48/2.68-7/35 °C (floor)
8.67/3.62/2.406.42/2.72/2.364.75/2.07/2.292/55 °C
6.75/1.74/3.885.00/1.31/3.823.70/1.00/3.707/45 °C
9.18/2.98/3.086.80/2.24/3.045.03/1.70/2.962/45 °C
12.01/5.36/2.248.90/4.03/2.216.58/3.06/2.15-7/45 °C
9.36/5.31/1.766.94/3.99/1.745.13/3.03/1.69-15/45 °C
6.38/2.04/3.134.73/1.54/3.073.50/1.17/2.997/55 °C
9.66/4.69/2.067.15/3.53/2.035.29/2.68/1.97-7/55 °C
MaxMaxMaxOutd. temp: /
Supply temp.
Cooling
13.30/3.99/3.339.87/3.16/3.137.52/2.37/3.1727/7 °C
Output data according to EN14511 ΔT5K
17.70/4.52/3.9111.70/3.32/3.5211.20/3.20/3.5027/18 °C
Specified/supplied power/EER
13.04/4.53/2.889.45/3.41/2.777.10/2.65/2.6835/7 °C
15.70/5.04/3.1211.20/3.58/3.129.19/2.98/3.0835/18 °C
Electrical data
230V 50 Hz, 230V 2AC 50HzRated voltage
252316A
rms
Max operating current, heat pump
242215A
rms
Max operating current, compressor
555A
rms
Starting current
---OhmMax permitted impedance at connection point
1)
2 x 868686WNominal output, fan
252516A
rms
Fuse
2)
Refrigerant circuit
R410AType of refrigerant
Twin RotaryType of compressor
M-MA68Compressor oil
4.02.92.55kgVolume
4.15 (41.5 bar)MPaCut-out value pressostat HP
0.079 (0.79 bar)MPaCut-out value pressostat LP
Brine
600043803000m
3
/hAirflow
-20/43°CMax/Min air temp
reverse cycleDefrosting system
Heating medium
0.05/0.25 (0.5/2.5bar)MPaMin/Max system pressure heating medium
1508050lMin volume, climate system, heating/cooling
15010080lMin volume, climate system, under floor cooling
0.790.570.38l/sMax flow, climate system
103Chapter 8 | Technical dataNIBE™ F2040