294 - NIBE F2040 + VVM 310/320/500 - Incompatible outdoor unit
Are the indoor unit and
outdoor unit compatible?
YES
YES
OK.
Action.
Replace the circuit board.
Check the DIP switches
according to the instructions
below.
Red in ON mode
Blue in OFF mode
Start the machine?
NO
NO
The DIP switches on the circuit board that state capacity of the outdoor unit can move out of position which results
in alarm 294.
To rectify this follow the instructions below:
Action F2040-8
Cut the power to the machine.
Open the outdoor unit, remove the cover.
Slacken off and remove the cover of the electrical distribution box.
Locate DIP switch JSW10 and JSW11 on the inverter board (PWB2), which is recessed to the left in the junction
box (see image).
Change mode back and forth on the switches several times and reset them to the original position.
Reinstall the covers.
Start the machine.
JSW11
PWB 2
JSW10
73Chapter 6 | TroubleshootingNIBE™ F2040

Table of Contents

Other manuals for Nibe F2040

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Nibe F2040 and is the answer not in the manual?

Nibe F2040 Specifications

General IconGeneral
TypeAir/water heat pump
RefrigerantR410A
Operating Temperature Range Heating-20°C to 35°C
Operating Temperature Range Cooling10°C to 46°C
Sound Power Level56-62 dB(A) (depending on model)

Related product manuals