EasyManua.ls Logo

Nibe FIGHTER 1120 - Control System Operation; Interface and Temperature Settings

Nibe FIGHTER 1120
76 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Commissioning and adjusting
FIGHTER 1120
34
Rotation check
Fighter 1120-15, 17 kW 3x400 V
Rotation check
Fighter 1120-12 kW 3x400 V
The compressor in FIGHTER 1120-12 kW 3 x400 V is
of the scroll type. It can only operate in one direction
of rotation. Operating in the wrong direction can
damage the compressor.
The direction of rotation is checked as follows:
Set the switch to 1.
Check the hot gas temperature in menu 5.11. The
temperature should increase by 10 °C within 30
seconds from compressor start.
If the temperature remains the same, the direction
of rotation is incorrect. The noise produced is also
different when rotating in the incorrect direction.
- Set the switch to 0 and cut the main
power supply.
- Swap the two incoming phases on the
terminal block for incoming electricity, -X9.
- Set the switch to 1 and check the rotation
again.
The compressor in FIGHTER 1120-15, 17 kW
3 x400 V is of the scroll type. It can only operate in
one direction of rotation. Operating in the wrong
direction can damage the compressor.
The direction of rotation is checked as follows:
Set the switch to 1.
Wait until the symbol for the compres-
sor lights up in the display.
Check that the compressor is operating.
If the compressor is not operating and the symbol
for the compressor is lit, there is a phase sequence
error. The phase sequence monitor (164) also indi-
cates this; see section “Electrical connection”.
- Set the switch to 0 and cut the main
power supply.
- Swap the two incoming phases on the
terminal block for incoming electricity, -X9.
- Set the switch to 1 and check the rotation
again.
PEN
L
1
L
2
L
3
-X9

Table of Contents

Other manuals for Nibe FIGHTER 1120

Related product manuals