Safety
information
Product
information
Mechanical
installation
Electrical
installation
Getting
started
Running the
motor
Drive parameters Communications Diagnostics Technical data
UL Listing
Information
10 Commander S100 User Guide
Table 2-2 200 V Drive ratings (200 to 240 V ±10 %)
Table 2-3 400 V Drive ratings (380 to 480 V ±10 %)
2.6.1 Drive overload limits
Typical short-term overload limits
The drive is rated to supply 150 % output current as an overload, such as when the motor is accelerating. During overload conditions, the internal
drive components get hot which limits the potential time the overload can be sustained.
Typical values are shown in the table below:
Model
Supply
P
hases
Maximum Continuous
Output Current
Peak Current Nominal Power at 230 V Motor power at 230 V
AA
kW hp
S100-01S13 1 1.4 2.1 0.18 0.25
S100-01213 3 1.4 2.1 0.18 0.25
S100-02S11 1 1.2 1.8 0.18 0.25
S100-01S23 1 1.6 2.4 0.25 0.33
S100-01223 3 1.6 2.4 0.25 0.33
S100-02S21 1 1.4 2.1 0.25 0.33
S100-01S33 1 2.4 3.6 0.37 0.5
S100-01233 3 2.4 3.6 0.37 0.5
S100-02S31 1 2.2 3.3 0.37 0.5
S100-01S43 1 3.5 5.25 0.55 0.75
S100-02S41 1 3.2 4.8 0.55 0.75
S100-01243 3 3.5 5.25 0.55 0.75
S100-01S53 1 4.6 6.9 0.75 1
S100-01253 3 4.6 6.9 0.75 1
S100-02S51 1 4.2 6.3 0.75 1
S100-01D63 1 / 3 6.6 9.9 1.1 1.5
S100-02S61 1 6 9 1.1 1.5
S100-01D73 1 / 3 7.5 11.25 1.5 2
S100-02S71 1 6.8 10.2 1.5 2
S100-03D13 1 / 3 10.6 15.9 2.2 3
Model
Supply
P
hases
Maximum Continuous
Output Current
Peak Current Nominal Power at 400 V Motor power at 460 V
AA
kW hp
S100-02413 3 1.2 1.8 0.37 0.5
S100-02423 3 1.7 2.55 0.55 0.75
S100-02433 3 2.2 3.3 0.75 1
S100-02443 3 3.2 4.8 1.1 1.5
S100-02453 3 3.7 5.55 1.5 2
S100-02463 3 5.3 7.95 2.2 3
S100-03413 3 7.2 10.8 3 3
S100-03423 3 8.8 13.2 4 5
Starting Condition
From Cold
(No previous output current)
From Hot
(Operating at 100 % output current)
Drive Output Current 150 % for 60 s 150 % for 8 s
The thermal protection may, in some cases, allow the drive to exceed these ratings. It is not recommended to run beyond the rating of the
drives as that will reduce the lifetime of the product and potentially void the warranty.
CAUTION