60 Commander S100 User Guide
7.3 Parameter descriptions
This section provides detailed descriptions on the functions of all parameters within the drive.
7.3.1 Menu 1 - Status & monitoring (Read only)
This menu contains all parameters that show an output variable of the drive for status and monitoring purposes. All parameters in this menu are read-
only.
The majority of parameters are numbers that can be easily interpreted on the drive display. For indicator parameters, such as Alarm Indicators
(P1.09), the drive displays an active bit with the 7-segment LEDs as shown in Figure 7-1 where bit 3 is active (1).
Figure 7-1 Binary parameter display
Bit 1
2
34567
0
P1.01 Output Frequency
Range: ± Maximum Frequency Limit (P2.02) Hz Default: Read Only
Displays the drive output frequency in Hz. This is the sum of the RampOutput(P1.14) and motor slip compensation. A positive value is used for
forward rotation, a negative value is used for reverse rotation.
The range stated above applies for when the Output Frequency is used as an input or output such as when represented on T6 Analog Output. The
parameter may extend outside of this range if slip compensation hasn't been disabled or if the motor is being driven by another part of the machine
faster than the maximum frequency limit.
P1.02 Output Voltage
Range: 0 to Maximum Supply Voltage V (100 V & 200 V Drive = 240 V, 400 V Drive = 480 V) Default: Read Only
Displays ther.m.s. line to line voltage at the output terminals of the drive. (U to V; V to W; W to U.)
The range stated above applies for when the Output Voltage is used as an input or output such as when represented on T6 Analog Output. The
parameter may extend outside of this range if the drive is decelerating with high motor voltage enabled.
P1.03 Output Power
Range: 0 to Drive Rated Power x 2.2 kW Default: Read Only
Displays the power flowing through the output terminals of the drive. This parameter should be used for indication purposes only. A positive value
indicates power flowing from the drive to the motor.
P1.04 Motor RPM
Range: ± 18000 rpm Default: Read Only
Displays the motor RPM. The Ramp Output (P1.14) is converted to the equivalent RPM using the number of motor poles. The actual motor RPM
could be lower if Motor Rated Speed (P3.02) is not set correctly.
P1.05 Drive State
Range: 0 to 17 Default: Read Only
Displays the present state of the drive as described below:
NOTE
NOTE
Value Drive State Description
0 Inhibited The drive is not enabled
1 Ready The drive is enabled but has not received a run signal
4 Running The drive is running
5 Supply Loss Supply loss has been detected
6 Deceleration The drive is stopping the motor with a decelerating ramp
7 Injecting D.C The drive is injecting D.C. braking current into the motor
9 Error The drive in an error state, check the error log for more information
15 Under Voltage The drive is in the under-voltage state
17 Initialising The drive systems are initialising