Safety
information
Product
information
Mechanical
installation
Electrical
installation
Getting started
Running the
motor
Drive
parameters
Communications Diagnostics Technical data
UL Listing
Information
Commander S100 User Guide 61
P1.06 Output Current
Range: ± Drive Rated Current x 2.2 A Default: Read Only
This displays the total output current to the motor. This is made up of two components, motor magnetising current and motor Torque Producing
Current(P1.07).
P1.07 Torque Producing Current
Range: ± Drive Rated Current x 2.2 A Default: Read Only
This parameter displays the component of the Output Current (P1.06) that is in phase with the voltage and does not include the magnetising current
of the motor.
This torque includes the load torque and acceleration torque.
If the Output Frequency is positive (forward rotation), a positive value of Torque Producing Current would hold the motor load or cause the motor to
accelerate.
If the Output Frequency is negative (reverse rotation), a negative value of torque producing current would hold the motor load or cause the motor to
accelerate.
The value is proportional to the torque produced by the motor provided the frequency applied to the motor is at or below the motor rated frequency.
P1.08 Percentage Load
Range: ± Torque Current Maximum Limit % Default: Read Only
This indicates the load on the motor as a percentage of the motor rated torque.
For forward rotation, this value is positive for a motoring load and negative for a regenerating load. For reverse rotation this value is negative for a
motoring load and positive for a regenerating load.
PercentageLoad(P1.08)=TorqueProducingCurrent(P1.07)/I
Trated
x 100
I
Trated
= Rated Torque Current = Motor Rated Current (P3.01) x Motor Rated Power Factor (P3.04)
P1.09 Alarm Indicators
Range:
0
7
0
6
0
5
0
4
0
3
0
2
0
1
0
0
to 1
7
1
6
1
5
1
4
1
3
1
2
1
1
1
0
Default: Read Only
An alarm is used by the drive to give an early warning of a problem which could lead to a drive error. The display will indicate an alarm condition by
flashing the display alarm indicators shown below. By default, in some alarm conditions, the drive may take action to prevent an error for example
reducing the motor current or speed.
Find additional information in Marshal or in section 9.1 Alarms.
P1.10 Drive Status Indicators
Range:
0
7
0
6
0
5
0
4
0
3
0
2
0
1
0
0
to 1
7
1
6
1
5
1
4
1
3
1
2
1
1
1
0
Default: Read Only
Displays a set of drive status indicators.
Bit
Display
Alarm
Indicator
Alarm How to remove the alarm
Bit0 A.0 Motor Overload Reduce the load on the motor
Bit1 A.1 Drive Overload Reduce the load on the motor or ambient temperature of the drive
Bit2 A.2 Auto-tune Active Will be reset when Autotune complete
Bit3 A.3 Limit Switch Rotate the motor away from the limit switch
Bit4 A.4 Supply Imbalance Check supply fuses to the drive
Bit5 A.5 Analog Current Check current loop master is powered and the integrity of the wiring is good
Bit6 A.6 Current Limit Reduce the load on the motor
Bit7 A.7 I/OOverload Check the 24 V output, digital output, and 485 port for an overload condition
Bit
Status
Description
Bit0 Supply Loss
Indicates supply loss has been detected. The behaviour in this situation is controlled by Supply Loss
Action (P4.08).
Bit1 Limit Switch Active
Indicates at least one limit switch is active.
Bit2 Thermal Limit Active
Indicates the output current is being limited further than that defined by Torque Current Limit (P3.17)
for thermal protection of the motor.
Bit3 Current Limit Active
Indicates the output current is being limited by the current limit defined by Torque Current Limit
(P3.17) or Bit 2 above.
Bit4 Drive Active
Indicates the drive is applying voltage to the motor.
Bit5 Healthy
Indicates the drive is healthy and there are no errors.
Bit6 At Speed±1Hz
Indicates the Ramp Output (P1.14) is within 1 Hz of the Ramp Input.
Bit7 At Zero ± 2 Hz
Indicates the Ramp Output (P1.14) is within 2 Hz of 0 Hz.