62 Commander S100 User Guide
P1.11 Sequencer Input and Output Indicators
Range:
0
7
0
6
0
5
0
4
0
3
0
2
0
1
0
0
to 1
7
1
6
1
5
1
4
1
3
1
2
1
1
1
0
Default: Read Only
Displays the input and output states of the sequencer. The drive sequencer monitors inputs to control how the drive will run.
P1.12 Run & Direction Indicators
Range:
0
7
0
6
0
5
0
4
0
3
0
2
0
1
0
0
to 1
7
1
6
1
5
1
4
1
3
1
2
1
1
1
0
Default: Read Only
Displays the states of the drive control inputs.
The indicators that are shown here can be set by any of the control terminals using their function selector parameters such as T11 Digital Input 1
Function Select (P6.16) or by the control word.
P1.13 Ramp Input
Range: ± Maximum Frequency Limit (P2.02) Hz Default: Read Only
Displays the selected reference frequency after the skip band and frequency limits have been applied but before it is fed into the ramp system. See
section 7.3.2 Menu 2 - References & Ramps.
P1.14 Ramp Output
Range: ± Maximum Frequency Limit (P2.02) Hz Default: Read Only
Displays the frequency output from the ramp system.
The range stated above applies for when the Ramp Output is used as an input or output such as when represented on T6 Analog Output. The
parameter may extend outside of this range if the motor is being driven by another part of the machine faster than the maximum frequency limit.
P1.15 T2 Analog Input 1 Percentage
P1.16 T4 Analog Input 2 Percentage
P1.17 T15 Frequency Input Percentage
Range: ± 100.00 % Default: Read Only
Displays the level of analog input 1, analog input 2 and the frequency input as a percentage after it has been scaled according to the terminal's
scaling parameters. See T2 Analog Input 1 Minimum Input (P6.21).
These values can be used for speed control by selecting an appropriate configuration in Frequency Reference Configuration (P2.03) or by selecting
the function in Frequency Reference 1 Selector (P2.21) to Frequency Reference 4 Selector (P2.24). When selected for speed control, 100 % is the
Maximum Frequency Limit (P2.02).
Bit
Status
Description
Bit 0 Hardware Enable
Set to 1 if a digital input has been configured as the Hardware Enable function (1) and is active, or if
no digital input has been configured as a Hardware Enable.
Bit 1 Software Enable
If the Binary Control Word (P4.18) is enabled this is set to 1 when the enable bit of the control word is
set otherwise this is set to 1 if Drive Enable (P4.17) is set to true.
Bit 2 Limit Switch Forward
Set to 1 if a digital input has been configured as the Forward Limit Switch (5) and is active. If set to 1
the drive can only run the motor in reverse.
Bit 3 Limit Switch Reverse
Set to 1 if a digital input has been configured as the Reverse Limit Switch (6) and is active. If set to 1
the drive can only run the motor forward.
Bit 4 Run Set to 1 when a run signal is detected.
Bit 5 Reverse Set to 1 when a Reverse signal is detected to reverse the selected reference.
Bit 6 Jog Set to 1 by the sequencer to select the Jog reference when a Jog signal is detected.
Bit 7 Under Voltage Set to 1 by the sequencer if the drive is in an under voltage state.
Bit
Status
Description
Bit 0 Run Forward Set to 1 if a Run Forward signal is active
Bit 1 Run Reverse Set to 1 if a Run Reverse signal is active.
Bit 2 Run Set to 1 if a Run signal is active.
Bit 3 Reverse Set to 1 if a Reverse signal is active.
Bit 4 Jog Forward Set to 1 if a Jog Forward signal is active.
Bit 5 Jog Reverse Set to 1 if a Jog Reverse signal is active.
Bit 6
Run Permit
(Not Stop)
Set to 1 if a Run Permit (Not Stop) signal is active.
Bit 7 Fire Mode Active Set to 1 if a Fire Mode signal is active.