Safety
information
Product
information
Mechanical
installation
Electrical
installation
Getting
started
Running the
motor
Drive
parameters
Communications Diagnostics Technical data
UL Listing
Information
Commander S100 User Guide 21
4.2 Terminal torque settings
To avoid a fire hazard and maintain validity of the UL listing, adhere to the specified tightening torques for all terminals.
Table 4-1 Drive power terminal torque settings
4.3 Cable selection
IEC cable sizes assume copper conductor, PVC insulation, installation method B2 and ambient temperature of 40 °C (104 °F). For UL, cables must
be rated for 60 °C (140 °F) operation and copper only. Cables must be provided with mechanical protection against damage and be rated for a
voltage in excess of the maximum supply voltage.
Table 4-2 Cable ratings (100 V Drive)
Table 4-3 Cable ratings (200 V Drive)
Cables marked † need to be rated for 90 °C and 1.5 mm
2
in order to terminate with a ferrule.
Cables marked †† need to be rated for 90 °C and 4 mm
2
in order to terminate with a ferrule.
Drive Voltage Rating 100 V 200 V 400 V
Recommended
Torque Setting
Power Connections 0.5 Nm (4.4 lb in) 0.6 Nm (5.3 lb in)
Ground Connections 1.5 Nm (13.3 lb in)
Control Connections (Including Relay) 0.4 Nm (3.5 lb in)
The nominal cable sizes below are for guidance only. The mounting and grouping of cables will affect their current-carrying capacity, in
some cases smaller cables may be acceptable but in other cases a larger cable is required to avoid excessive temperature or voltage drop.
Refer to local wiring regulations for the correct size of cables.
Model Number Supply Phases
Cables IEC60364-5-52
mm²
UL61800-5-1
AWG
Supply Motor
Supply
Motor
Nominal Maximum Nominal Maximum Nominal Maximum Nominal Maximum
S100-01113 1 1.5 2.5 1.5 2.5 24 12 24 12
S100-01123 1 1.5 2.5 1.5 2.5 24 12 24 12
S100-01133 1 1.5 2.5 1.5 2.5 22 12 22 12
S100-03113 1 2.5 6 1.5 2.5 20 8 20 12
S100-03123 1 2.5 6 1.5 2.5 18 8 18 12
S100-03133 1
6
††
61.52.51681612
Model Number Supply Phases
Cables IEC60364-5-52
mm²
UL61800-5-1
AWG
Supply Motor
Supply
Motor
Nominal Maximum Nominal Maximum Nominal Maximum Nominal Maximum
S100-01S13 1 1.5 2.5 1.5 2.5 24 12 24 12
S100-01213 3 1.5 2.5 1.5 2.5 24 12 24 12
S100-02S11 1 1.5 2.5 1.5 2.5 24 12 24 12
S100-01S23 1 1.5 2.5 1.5 2.5 24 12 24 12
S100-01223 3 1.5 2.5 1.5 2.5 24 12 24 12
S100-02S21 1 1.5 2.5 1.5 2.5 24 12 24 12
S100-01S33 1 1.5 2.5 1.5 2.5 22 12 22 12
S100-01233 3 1.5 2.5 1.5 2.5 22 12 22 12
S100-02S31 1 1.5 2.5 1.5 2.5 22 12 22 12
S100-01S43 1 1.5 2.5 1.5 2.5 20 12 20 12
S100-01243 3 1.5 2.5 1.5 2.5 20 12 20 12
S100-02S41 1 1.5 2.5 1.5 2.5 20 12 20 12
S100-01S53 1 1.5 2.5 1.5 2.5 18 12 18 12
S100-01253 3 1.5 2.5 1.5 2.5 18 12 18 12
S100-02S51 1 1.5 2.5 1.5 2.5 18 12 18 12
S100-01D63
1
2.5
†
2.5 1.5 2.5 16 12 16 12
3 1.5 2.5 1.5 2.5 16 12 16 12
S100-02S61 1
2.5
†
2.5 1.5 2.5 16 12 16 12
S100-01D73
1
2.5
†
2.5 1.5 2.5 16 12 14 12
3
2.5
†
2.5 1.5 2.5 16 12 14 12
S100-02S71 1
2.5
†
2.5 1.5 2.5 16 12 14 12
S100-03D13
1 4 6 1.5 2.5 14 8 14 12
3 4 6 1.5 2.5 14 8 14 12