112 Commander S100 User Guide
Power drive systems are categorized C1 to C4:
Table 10-5 Power drive system categories
10.4.1 Optional external EMC filters
Table 10-6 Drive and EMC filter cross reference
10.5 Maximum cable lengths
Since capacitance in the motor cable causes loading on the output of the drive, ensure the cable length does not exceed 50 m. For motor lengths to
comply to a particular EMC standard, such as C1, refer to the cable lengths given in section 10.4 Emission compliance .
10.6 Starts per hour
By electronic control: Unlimited
By interrupting the A.C. supply: ≤20 (equally spaced)
Category Definition
C1 Intended for use in the first or second environments
C2
Not a plug-in or movable device, and intended for use in the first environment only when installed by a professional, or in the
second environment
C3 Intended for use in the second environment, not the first environment
C4 Rated at over 1000 V or over 400 A, intended for use in complex systems in the second environment
Drive Model Number
Power Rating
(kW)
Power Rating
(hp)
Control Techniques Part Number
200 V Drive
S100-01S13 0.18 0.25
S100-01213 0.18 0.25
S100-01S23 0.25 0.33
S100-01223 0.25 0.33
S100-01S33 0.37 0.5
S100-01233 0.37 0.5
S100-01S43 0.55 0.75
S100-01243 0.55 0.75
S100-01S53 0.75 1
S100-01253 0.75 1
S100-01D63 1.1 1.5
S100-01D73 1.5 2
S100-03D13 2.2 3
400 V Drive
S100-02413 0.37 0.5
S100-02423 0.55 0.75
S100-02433 0.75 1
S100-02443 1.1 1.5
S100-02453 1.5 2
S100-02463 2.2 3
S100-03413 3 3
S100-03423 4 5