2.5 Date code format
The date code is provided in a four digit format. The first two digits indicate the year and the remaining two digits indicate the week number (within the
year).
Example:
A date code of 2110 would correspond to week 10 of year 2021.
2.6 Drive ratings
The continuous current ratings given below are for a maximum ambient temperature of 40 °C (104 °F), 1000 m altitude and
4 kHz switching
frequency. Derating may be required for higher switching frequencies, at an ambient
temperature > 40 °C (104 °F) and at higher altitude. For further
information, refer to section 10 Technical data
.
Table 2-1 100 V Drive ratings (100 to 120 V ±10 %)
The 100 V drive has a voltage doubler circuit on the input, therefore the rated output voltage is twice that of the supply and the motor used should
have a rated voltage appropriate for this.
Model
Supply
P
hases
Maximum Continuous
Output Current
Peak Current Nominal power at 200 V Motor power at 200 V
AA
kW hp
S100-01113 1 1.2 1.8 0.18 0.25
S100-01123 1 1.4 2.1 0.25 0.33
S100-01133 1 2.2 3.3 0.37 0.5
S100-03113 1 3.2 4.8 0.55 0.75
S100-03123 1 4.2 6.3 0.75 1
S100-03133 1 6 9 1.1 1.5