P2.24 Frequency Reference 4 Selector
Range: 0 to 9 Default: 0 (None)
These four parameters can be used to configure four individual references that the drive can use for speed control. For information on selecting
between these references see Frequency Reference 1 to 4 Switch (P2.20).
For inputs 0 - 4, the frequency references are transferred directly into the reference system. For inputs 5 - 9, the percentages selected are
converted to Hz using parameters Minimum Frequency Limit (P2.01) and Maximum Frequency Limit (P2.02).
Figure 7-6 Percent to Frequency scaling
If this parameter is set to 0 (None), the drive will run at the Minimum Frequency Limit (P2.01).
The value of these parameters can be set by Frequency Reference Configuration (P2.03).
Value Frequency Reference Description
0
None A fixed reference of 0 Hz
1
Preset 1 The frequency reference is defined by Preset Frequency 1 (P2.16)
2
Preset 2 The frequency reference is defined by Preset Frequency 2 (P2.17)
3
Preset 3
The frequency reference is defined by Preset Frequency 3 (P2.18)
4
Preset 4 The frequency reference is defined by Preset Frequency 4 (P2.19)
5
T2 Analog 1 % The frequency reference is derived from T2 Analog Percentage 1 (P1.15)
6
T4 Analog 2 % The frequency reference is derived from T4 Analog Percentage 2 (P1.16)
7
T15 Frequency % The frequency reference is derived from T15 Frequency Input Percentage (P1.17)
8
Up/Down Percent The frequency reference is derived from Up/Down Percentage (P1.18)
9
PID Percent The frequency reference is derived from PID Percentage (P1.19)