7.3.3 Menu 3 - Motor setup
This menu contains parameters relating to motor setup and control.
P3.01 Motor Rated Current
Range: 0.00 to Drive Rated Current (A) Default: Rating Dependent
Motor Rated Current must be set to the maximum continuous current of the motor (taken from the motor nameplate).
P3.02 Motor Rated Speed
Range: 0 to 18000 rpm Default: Region Dependent
Set to the rated speed of the motor from the motor nameplate for better speed control by allowing the drive to compensate for motor slip.
Slip compensation can be disabled by setting Motor Rated Speed to synchronous speed or 0. If Motor Rated Speed is set to 0, Number Of Motor
Poles (P3.16) must be set up manually for Motor RPM (P1.04) to indicate the correct speed.
P3.03 Motor Rated Voltage
Range: 0 to Maximum Drive Output Voltage Default: Rating Dependent
Motor Rated Voltage must be set to the voltage rating of the motor (taken from the motor nameplate).
Motor Rated Voltage and Motor Rated Frequency (P3.15) define the voltage to frequency characteristic applied to the motor. See Motor Control
Mode (P3.05) for more details.
P3.04 Motor Rated Power Factor
Range: 0.00 to 1.00 Default: Rating Dependent
Motor Rated Power Factor is the rated power factor of the machine, cos φ (taken from the motor nameplate).
Drive Voltage Rating Region Maximum Drive Output Voltage Default
100 V
All
240 V 230 V
200 V
400 V
50 Hz
480 V 400 V
60 Hz
480 V 460 V