P5.15 Threshold Detector Delay
Range: -25.0 to 25.0 s Default: 0.0 s
If set to a positive value then the Threshold Output does not become On (1) until the input has been above the threshold for the programmed
period of time. If set to a negative value then the Threshold Output remains On (1) until the input has been below the threshold for the programmed
period of time.
Figure 7-16 Threshold Detector - Positive Delay
Figure 7-17 Threshold Detector - Negative Delay
P5.16 Threshold Detector Output Invert
Range: 0 to 1 Default: 0
Set to 1 to invert the logic level from the Threshold Detector.
The Threshold Detector output is shown in bit 2 of PID Status Indicators (P1.20).