Digistart D3: User Guide 63
Issue: G
Parameter Group
Parameters
Default Value
12 - Start/Stop Modes-2
M
12A
Start Mode-2
Constant Current
12B
Current Limit-2
350%
12C
Initial Current-2
350%
12D
Start Ramp-2
00:10 (minutes:seconds)
12E
Adaptive Start Profile-2
Constant Acceleration
12F
Kickstart Level-2
500%
12G
Kickstart Time-2
0 ms
12H
Stop Mode-2
Coast To Stop
12I
Stop Time-2
00:03 (minutes:seconds)
12J
Stop Delay-2
00:00 (minutes:seconds)
12K
Adaptive Stop Profile-2
Constant Deceleration
12L
Adaptive Control Gain-2
75%
12M
Brake Torque-2
20%
12N
Brake Time-2
00:01 (minutes:seconds)
13 - Slip-Ring Motors
M
13A
Motor Data-1 Ramp
Single Ramp
13B
Motor Data-2 Ramp
Single Ramp
13C
Slip Ring Retard
50%
13D
Changeover Time
150 ms
14 - RTD/PT100
M
14A
RTD/PT100 A °C
50 °C
14B
RTD/PT100 B °C
50 °C
14C
RTD/PT100 C °C
50 °C
14D
RTD/PT100 D °C
50 °C
14E
RTD/PT100 E °C
50 °C
14F
RTD/PT100 F °C
50 °C
14G
RTD/PT100 G °C
50 °C
15 - Restricted
M
15A
Access Code
0000
15B
Emergency Run
Disable
15C
Adjustment Lock
Read & Write
15D
Shorted SCR Action
3-Phase Control Only
15E
Jog Torque
50%