NE200&300 Quick Start Guide
44
Code
Description
Setting range Default Modify
Modbus
Address
terminal open
F6.32
Pos. and Neg.
logic terminal
X 1
Pos. logic of Xi
terminal:
Be valid while
connecting between Xi
and COM.
Neg. logic of Xi
terminal:
Be valid while
disconnecting
between Xi and COM.
Units: Logic of X1
terminal
Tens: Logic of X2
terminal
Hundreds: Logic of X3
terminal
Thousands: Logic of
X4 terminal
0000 × 0720H
F6.33
Pos. and
Neg. logic
terminal X 2
Units: Logic of X5
terminal
Tens: Logic of AI1
terminal
Hundreds: Logic of
AI2 terminal
Note:
Terminal
24
25
26
27
42
43
44 and 49 are not
impacted by this
parameter.
0000 × 0721H
F6.33
Pos. and
Neg. logic
terminal X 2
Units: Logic of X5
terminal
Tens: Logic of X6
terminal
Hundreds: Logic of X7
terminal
0721H