EasyManua.ls Logo

Nidec NE200 Series - Page 57

Nidec NE200 Series
73 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
NE200&300 Quick Start Guide
56
Code
Description Setting range Default
Modify
Modbus
Address
protection mode 1: Common motor
(with low speed
compensation)
2: Variable
frequency motor
(without low speed
compensation)
FC.01
Electro thermal
protection value
20
110% 100% 0D01H
FC.02
Overload
Pre-alarm
detection level
30.0
200.0% 160% 0D02H
FC.03
Overload
Pre-alarm
detection time
0.0
80.0s 60.0s 0D03H
FC.04
Current amplitude
limit
0:Invalid
2
0D04H
1: Acc./Dec. valid;
Constant speed
invalid
2: Valid all the time
FC.05
Current amplitude
limit level
Type G
80.0
200.0%
G:
160.0%
0D05H
Type P
60.0
150.0%
P:
120.0%
FC.06
Over voltage stall
function
0: Invalid
(Recommended if
braking resistor
mounted)
1 ×
0D06H
1: Valid for Acc/Dec.
2: Valid all the time
FC.07
Overvoltage point
for Acc./Dec.
suspend
110.0
150.0%
(Bus voltage)
380V:
140%
× 0D07H
220V:
120%

Related product manuals