5 Parameters
BU 0505 EN-3021 111
P312
Torque current controller P
(Torque current controller P)
S P
0 ... 1000 %
{ 400 }
Current controller for the torque current. The higher the current controller parameters are set, the
more precisely the current setpoint is maintained. Excessively high values in P312 generally lead
to high-frequency oscillations at low speeds; on the other hand, excessively high values in P313
generally produce low frequency oscillations across the whole speed range.
If the value "Zero" is entered in P312 and P313, then the torque current control is switched off. In
this case, only the motor model pre-control is used.
Pos: 184 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P300- P399/Parameter P313 Moment enstromregler I @ 0\mod_1327591883202_388.doc x @ 8603 @ @ 1
P313
Torque current controller I
(Torque current controller I)
S P
0 ... 800 % / ms
{ 50 }
I-proportion of the torque current controller. (See also P312 >Torque current controller P<)
Pos: 185 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P300- P399/Parameter P314 Gren ze M.-stromregl. @ 0\mod_1327 591927202_388.doc x @ 8626 @ @ 1
P314
Torque current controller limit
(Torque current controller limit)
S P
0 ... 400 V
{ 400 }
Determines the maximum voltage increase of the torque current controller. The higher the value,
the greater the maximum effect that can be exercised by the torque current controller. Excessive
values in P314 can specifically lead to instability during transition to the field weakening zone (see
P320). The values for P314 and P317 should always be set roughly the same, so that the field
and torque current controllers are balanced.
Pos: 186 /Anleitungen/ Elektronik/F U und Starter/5. Parameter /Parameterauflis tung (P000 ...)/ P300-P399/Parameter P315 Felds tromregler P @ 1\mod_1328 618593561_388.doc x @ 15410 @ @ 1
P315
Field current controller P
(Field current controller P)
S P
0 ... 1000 %
{ 400 }
Current controller for the field current. The higher the current controller parameters are set, the
more precisely the current setpoint is maintained. Excessively high values for P315 generally lead
to high frequency vibrations at low speeds. On t
he other hand, excessively high values in P316
generally produce low frequency vibrations across the whole speed range If the value "Zero" is
entered in P315 and P316, then the field current controller is switched off. In this case, only the
motor model pre-control is used.
Pos: 187 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P300- P399/Parameter P316 Felds tromregler I @ 0\mod_132759 2705182_388.doc x @ 8676 @ @ 1
P316
Field current controller I
(Field current controller I)
S P
0 ... 800 % / ms
{ 50 }
I-proportion of the field current controller. See also P315 >Field current controller P<
Pos: 188 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P300- P399/Parameter P317 Gren ze Feldstromregl @ 0\mod_ 1327592747463_388.doc x @ 8699 @ @ 1
P317
Field current controller limit
(Field current controller limit)
S P
0 ... 400 V
{ 400 }
Determines the maximum voltage increase of the field current controller. The higher the value, the
greater is the maximum effect that can be exercised by the field current controller. Excessive
values in P317 can specifically lead to instability during transition to the field reduction range (see
P320). The values for P314 and P317 should always be set roughly the same, so that the field
and torque current controllers are balanced.
Pos: 189 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P300- P399/Parameter P318 Feldsc hwächregler P @ 0\mod_132 7592793650_388.doc x @ 8722 @ @ 1
P318
Field weakening controller P
(Field weakening controller P)
S P
0 ... 800 %
{ 150 }
The field weakening controller reduces the field setpoint when the synchronous speed is
exceeded. Generally, the field weakening controller has no function; for this reason, the field
weakening controller only needs to be set if speeds are se
t above the nominal motor speed.
Excessive values for P318 / P319 will lead to controller oscillations. The field is not weakened
sufficiently if the values are too small or during dynamic acceleration and/or delay times. The
downstream current controller can no longer read the current setpoint.