SK 54xEUsers Manual for Frequency Inverters
112 BU 0505 EN-3021
P319
Field weakening controller I
(Field weakening controller I)
S P
0 ... 800 % / ms
{ 20 }
Only affects the field weakening range, see P318 >Field weakening controller P<
Pos: 191 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P300- P399/Parameter P320 Gren ze Feldschwächregler @ 0\mod_1327677173911_388.d ocx @ 8773 @ @ 1
P320
Field weakening limit
(Field weakening limit)
S P
0 ... 110 %
{ 100 }
The field weakening limit determines at which speed / current the controller will begin to weaken
the field. At a set value of 100% the controller will begin to weaken the field at approximately the
synchronous speed.
If values much larger than the standard values have been set in P314 and/or P317, then the field
weakening limit should be correspondingly reduced, so that the control range is actually available
to the current controller.
Pos: 192 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P300- P399/Parameter P321 Dr ehzahlregler I Lüftzei t @ 0\mod_1327677231913_38 8.docx @ 8796 @ @ 1
P321
Speedctr. I brake off
(Speed control I brake release time)
S P
0 ... 4
{ 0 }
During the brake release time (P107/P114), the I component of the speed control is increased.
This leads to better load take-up, especially with vertical movements.
0 = P311 speed control l x 1
1 = P311 speed control l x 2
2 = P311 speed control l x 4
3 = P311 speed control l x 8
4 = P311 speed control l x 16
Pos: 193 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P300- P399/Parameter P325 Funk tion Drehgeber @ 0\mod_1327 677283553_388.doc x @ 8819 @ @ 1
P325
Rotary encoder function
(Rotary encoder function)
0 ... 4
{ 0 }
The actual speed list value supplied by an incremental encoder to the FI can be used for various
functions in the FI.
0 = Speed measurement Servo mode, "Servo mode speed measurement": The actual motor
speed list value is used for the FI servo mode. The ISD control cannot be switched off in this
function.
1 = PID actual frequency value: The actual speed of a system is used for speed control. This
function can also be used for controlling a motor with a linear characteristic curve. It is also
possible to use an incremental encoder for speed control which is not mounted directly onto
the motor. P413 P416 determine the control.
2 = Frequency addition: The determined speed is added to the actual setpoint value.
3 = Frequency subtraction: The determined speed is subtracted from the actual setpoint.
4 = Maximum frequency: The maximum possible output frequency / speed is limited by the
speed of the encoder.
Pos: 194 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P300- P399/Parameter P326 Dr ehgeber Übersetzung @ 0\mod_13 27677354896_388. docx @ 8842 @ @ 1
P326
Ratio encoder
(Encoder transformation ratio)
0.01 ... 100.00
{ 1.00 }
If the incremental encoder is not mounted directly onto the motor shaft, then the respectively
correct transformation ratio of motor speed to encoder speed must be set.
speed Encoder
speed Motor
P326 =
Only when P325 = 1, 2, 3 or 4, therefore not in Servo mode (motor speed control)
Pos: 195 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P300- P399/Parameter P327 Sc hleppfehler Drehzah lregler @ 0\mod_132767740 6270_388.docx @ 8865 @ @ 1