SK 54xE – Users Manual for Frequency Inverters
120 BU 0505 EN-3021
P402 [-01]
...
[-06]
Adjustment: 0%
(Analog input adjustment: 0%)
S
-50.00 ... 50.00 V
{ all 0.00 }
This parameter sets the voltage that should correspond with the minimum value of the selected
function for the analog input.
[-01] = Analog input 1: analog input 1, integrated into the FI
[-02] = Analog input 2: analog input 2, integrated into the FI
[-03] = External analog input 1, "External analog input 1": Analog input 1 of the first IO extension
[-04] = External analog input 2, "External analog input 2": Analog input 2 of the first IO
extension
[-05] = External Analog input 1, 2nd IOE, "External analog input 1 of the 2nd IOE": Analog
input 1 of the second IO extension
[-06] = External Analog input 2, 2nd IOE, "External analog input 2 of the 2nd IOE": Analog
input 2 of the second IO extension
Typical setpoints and corresponding settings:
0 – 10 V 0.00 V
2 – 10 V 2.00 V (monitored for function 0-10 V)
0 – 20 mA 0.00 V (internal resistance approx. 250 Ω)
4 – 20 mA 1.00 V (internal resistance approx. 250 Ω)
Pos: 225 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/ P400-P499/Parameter P403 – Abg leich Analogeingang: 100% [SK 1x0E, SK 54xE] @ 0\mod_1327 681136791_388.doc x @ 9257 @ @ 1
P403 [-01]
...
[-06]
Adjustment: 100%
(Analog input adjustment: 100%)
S
-50.00 ... 50.00 V
{ all 0.00 }
This parameter sets the voltage that should correspond with the maximum value of the selected
function for the analog input.
[-01] = Analog input 1: analog input 1, integrated into the FI
[-02] = Analog input 2: analog input 2, integrated into the FI
[-03] = External analog input 1, "External analog input 1": Analog input 1 of the first IO extension
[-04] = External analog input 2, "External analog input 2": Analog input 2 of the first IO
extension
[-05] = External Analog input 1, 2nd IOE, "External analog input 1 of the 2nd IOE": Analog
input 1 of the second IO extension
[-06] = External Analog input 2, 2nd IOE, "External analog input 2 of the 2nd IOE": Analog
input 2 of the second IO extension
Typical setpoints and corresponding settings:
0 – 10 V 10.00 V
2 – 10 V 10.00 V (monitored for function 0-10 V)
0 – 20 mA 5.00 V (internal resistance approx. 250 Ω)
4 – 20 mA 5.00 V (internal resistance approx. 250 Ω)