5 Parameters
BU 0505 EN-3021 121
P400 ... P403
P401 = 0 0 - 10V limited
0.0V
2.5V
5.0V
10.0V
P105
P104
P402
P403
P401 = 1 0 - 10V not limited
0.0V
2.5V
5.0V
10.0V
P105
P104
P402
P403
Pos: 228 /Anleitun gen/Elektronik/F U und Starter/5. Parameter /Parameterauflis tung (P000 ...)/ P400-P499/Parameter P404 – Fi lter Analogeingang [SK 1 x0E, SK 2xxE, SK 54xE] @ 0\mod_13276 81301144_388.doc x @ 9326 @ @ 1
P404 [-01]
[-02]
Analogue input filter
(analogue input filter)
S
1 ... 400 ms
{ all 100 }
Adjustable digital low-
pass filter for the analogue signal. Interference peaks are hidden, the
reaction time is extended.
[-01] = Analogue input 1: analogue input 1 integrated in the device
[-02] = Analogue input 2: analogue input 2 integrated in the device
The filter time for the analogue inputs of the optional external IO extension modules is set in the
parameter set for the relevant module (P161).
Pos: 234 /Anleitun gen/Elektronik/F U und Starter/5. Parameter /Parameterauflis tung (P000 ...)/ P400-P499/Parameter P410 – Mini malfrequenz Nebenso llwerte @ 0\mod_132768161 7600_388.docx @ 9464 @ @ 1
P410
Min. freq. a-in 1/2
(Minimum frequency a-in 1/2 (auxiliary setpoint
value))
P
-400.0 ... 400.0 Hz
{ 0.0 }
The minimum frequency that can act on the setpoint via the auxiliary setpoints.
Auxiliary setpoints are all frequencies that are additionally delivered for further functions in the FI:
Actual frequency PID Frequency addition Frequency subtraction
Auxiliary setpoints via BUS Process controller
Min. frequency above analog setpoint (potentiometer)
Pos: 235 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P400- P499/Parameter P411 – Maxi malfrequenz Nebensol lwerte @ 0\mod_132794008748 6_388.docx @ 9490 @ @ 1
P411
Max. freq. a-in 1/2
(Maximum frequency a-in 1/2 (auxiliary setpoint
value))
P
-400.0 ... 400.0 Hz
{ 50.0 }
The maximum frequency that can act on the setpoint via the auxiliary setpoints.
Auxiliary setpoints are all frequencies that are additionally delivered for further functions in the FI:
Actual frequency PID Frequency addition Frequency subtraction
Auxiliary setpoints via BUS Process controller
Min. frequency above analog setpoint (potentiometer)
Pos: 236 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P400-P499/Parameter P412 – Sollwert Pr ozeßregler @ 0\mod_1327940 158248_388.doc x @ 9513 @ @ 1