SK 54xE – Users Manual for Frequency Inverters
130 BU 0505 EN-3021
List of possible functions of the relays and digital outputs
For the control of a mechanical brake on the motor. The relay switches at a
programmed absolute minimum
frequency (P505). For typical brakes a setpoint
delay of 0.2 … 0.3 seconds should be programmed (see also P107).
A mechanical brake may be directly switched by AC current. (Note the technical
specification of the relay contacts!)
the closed relay contact indicates voltage at the inverter output (U - V - W) (also DC
run-on(→ P559)).
Based on the setting of the motor rated current in P203. This value can be adjusted
with the standardisation (P435).
Based on motor data settings in P203 and P206. Signals a corresponding torque
load on the motor. This value can be adjusted with the standardisation (P435).
Based on motor nominal frequency setting in P201. This value can be adjusted with
the standardisation (P435).
indicates that the FI has completed the frequency increase or decrease. Setpoint
frequency = actual frequency! From a difference of 1 Hz Setpoint not reached -
contact opens.
General fault message, fault is active or not yet acknowledged.
Error: contact opens, ready: contact closes
General warning - a limit value was reached that could lead to a later shutdown of
the FI.
At least 130% of the nominal FI current was supplied for 30 seconds.
warning
Motor overtemperature (warning): The motor temperature is evaluated via the PTC
input or a digital input. Motor is too hot. Thi
s warning is given immediately,
overheating switch-off after 2 seconds.
active
Torque current limit/Current limit active (warning): The limiting value in P112 or P536
has been reached. A negative value in P435 inverts the reaction. Hysteresis = 10 %.
The output can be set using parameter P541 independently of the actual operating
status of the FI.
13 Generator torque current
limit
Limit value in P112 was reached in the generator range. Hysteresis = 10 %. High
... 17 Reserved
The FI is ready for operation. After being enabled it delivers an output signal.
… 29 reserved POSICON (BU 0510)
Control by Bus In Bit 0 (P546 …)
Control by Bus In Bit 1 (P546 …)
Control by Bus In Bit 2 (P546 …)
Control by Bus In Bit 3 (P546 …)
Control by Bus In Bit 4 (P546 …)
Control by Bus In Bit 5 (P546 …)
Control by Bus In Bit 6 (P546 …)
Control by Bus In Bit 7 (P546 …)
Value from bus setpoint (P546 …)
Details can be found in the bus manuals
The relay / bit deactivates if STO or the Safe Stop are active.
* For relay contacts (High = "Contact closed", Low = "Contact open")