5 Parameters
BU 0505 EN-3021 131
Parameter
{factory setting}
Setting value / Description / Note Supervisor
Parameter
set
Pos: 275 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P400- P499/Parameter P435 – Nor mierung Digitalausgän ge [SK 54xE] @ 0\mod_13280014 42849_388.doc x @ 10296 @ @ 1
P435 [-01]
...
[-05]
Dig. out scaling
(Scaling of digital output)
P
-400 ... 400 %
{ all 100 }
Adjustment of the limiting values of the digital functions. For a negative value, the output function
will be output negative.
[-01] = Output 1 / MFR1, relay output 1:
[-02] = Output 2 / MFR2, relay output 2:
[-03] = Output 3 / DOUT1, digital output 1
[-04] = Output 4 / DOUT2, digital output 2
[-05] = Output 5 / DOUT3, digital output 3
Reference to the following values:
Current limit (3) = x [%] ⋅ P203 >Rated motor current<
Torque current limit (4) = x [%] ⋅ P203 ⋅ P206 (calculated rated motor torque)
Frequency limit (5) = x [%] ⋅ P201 >Rated motor frequency<
Pos: 277 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P400- P499/Parameter P436 – Hys terese Digitalausgäng e [SK 54xE] @ 0\mod_132800157 2366_388.docx @ 10342 @ @ 1
P436 [-01]
...
[-05]
Dig. out. hysteresis
(Digital output hysteresis)
S P
1 ... 100 %
{ all 10 }
Difference between switch-on and switch-off point to prevent oscillation of the output signal.
[-01] = Output 1 / MFR1, relay output 1:
[-02] = Output 2 / MFR2, relay output 2:
[-03] = Output 3 / DOUT1, digital output 1
[-04] = Output 4 / DOUT2, digital output 2
[-05] = Output 5 / DOUT3, digital output 3
Pos: 287 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P400- P499/Parameter P460 – Zeit W atchdog @ 0\mod_1328002132 184_388.docx @ 10572 @ @ 1
P460
Time Watchdog
(Time Watchdog)
S
-250.0 ... 250.0 sec
{ 10.0 }
0.1 ... 250.0 = The time interval between the expected Watchdog signals (programmable function
of the digital inputs P420 – P425). If this time interval elapses without a pulse being
registered, switch off and error message E012 are actuated.
0.0 = customer error: As soon as a high-low flank or a low signal is detected at a digital input
(function 18) the FI switches off with error message E012.
-250.0 … -0.1 = Rotor running watchdog:
In this setting the rotor running watchdog is active.
The time is defined by the number of the value which has been set. When the FI is
switched off, there is no watchdog message. After each enable, a pulse must first
be received before the watchdog is activated.