SK 54xEUsers Manual for Frequency Inverters
138 BU 0505 EN-3021
P507
PPO-Type
(PPO-Type)
1 ... 4
{ 1 }
This parameter can only be used with the technology unit Profibus, DeviceNet or InterBus.
See also the relevant section of the corresponding supplementary BUS manual.
Pos: 312 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P500- P599/Parameter P508 Pr ofibus-Adresse @ 0\mod_132809 2017167_388.doc x @ 11065 @ @ 1
P508
Profibus address
(Profibus address)
1 ... 126
{ 1 }
Profibus address, only with the technology unit Profibus
See also the additional description for the Profibus control BU 0020
Pos: 313 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P500- P599/Parameter P509 Quel le Steuerwort @ 0\mod_13280921 04264_388.doc x @ 11088 @ @ 1
P509
Source Control Word
(Source control word)
0 ... 10
{ 0 }
Selection of the interface via which the FI is controlled.
0 = Control terminals or keyboard control ** with the ControlBox (if P510=0), the
ParameterBox (not ext. p-box) or via BUS I/O Bits.
1 = Only control terminals , the FI can only be controlled via the digital and analog inputs or via
the bus I/O Bits.
2 = USS control word *, the control signals (enable, direction of rotation, ...) are transferred via the
RS485 interface. The setpoint is transferred via the analog input or the fixed frequencies.
This setting should also be selected if communication via Modbus RTU is intended. The
frequency inverter automatically detects whether this is a USS protocol or a Modbus
protocol.
3 = CAN control word *
4 = Profibus control word *
5 = InterBus control word *
6 = CANopen control word *
7 = DeviceNet control word *
8 = Ethernet TU*** control word*
9 = CAN Broadcast *
10 = CANopen Broadcast *
*) Keyboard control (ControlBox, ParameterBox, PotentiometerBox) is blocked,
parameterisation is still possible.
**) If the communication during keyboard control is interrupted (time out 0.5 sec),
the FI will block without an error message.
***) The Ethernet TU setting must be used for all NORD Ethernet-based bus systems (e.g.:
EtherCAT: SK TU3-ECT, PROFINET: SK TU3-PNT).
Note:
Parameterisation of a frequency inverter via a field bus connection requires
parameter (P509) "Control Terminals" to be set to the appropriate bus system
Pos: 314 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P500- P599/Parameter P510 Quel le Sollwerte @ 0\mod_132809 2251176_388.doc x @ 11111 @ @ 1
P510 [-01]
[-02]
Setpoint source
(Setpoint source)
S
0 ... 10
{ all 0 }
Selection of the setpoint source to be parameterised.
[-01] = Main setpoint source [-02] = Auxiliary setpoint source
Selection of the interface via which the FI receives the setpoint.
0 = Auto (=P509): The source of the auxiliary setpoint is
automatically derived from the setting in the parameter
P509 >Interface<
1 = Control terminals, digital and analog inputs control the
frequency, including fixed frequencies
2 = USS (or Modbus RTU)
3 = CAN
4 = Profibus
5 = InterBus
6 = CANopen
7 = DeviceNet
8 = Ethernet TU
9 = CAN Broadcast
10 = CANopen Broadcast
Pos: 315 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P500- P599/Parameter P511 US S-Baudrate @ 0\mod_1328092296926_388.d ocx @ 11134 @ @ 1
NOTE:
For details about the respective Bus systems please
refer to the respective Options descriptions.
www.nord.com -