SK 54xEUsers Manual for Frequency Inverters
140 BU 0505 EN-3021
P515 [-01]
...
[-03]
CAN address
(CAN address)
0 ... 255
{ all 50 }
Setting of the basic CANbus address for CAN and CANopen. With the use of the CANopen
technology unit,
settings from this parameter are only valid if the BAUD rotary coding switch on
the technology unit has been set to PGM.
Information
Data takeover
The baud rate is only read after a Power On, a Reset Node message or a Power On of the
24V bus supply.
From software version 1.6 and above, this can be set in three levels:
[-01] = Slave address, Receipt address for CAN and CANopen (as before)
[-02] = Broadcast slave address, Broadcast receipt address for CANopen (Slave)
[-03] = Master address, Broadcast – Transmission address for CANopen (Master)
Pos: 322 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P500- P599/Parameter P516 Ausb lendfrequenz 1 @ 0\mod_132 8092606664_388.doc x @ 11249 @ @ 1
P516
Skip frequency 1
(Skip frequency 1)
S P
0.0 ... 400.0 Hz
{ 0.0 }
The output frequency around the frequency value (P517) set here is not shown.
This range is transmitted with the set brake and acceleration ramp; it cannot be continuously
supplied to the output. Frequencies below the absolute minimum frequency should not be set.
0 = Skip frequency inactive
Pos: 323 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P500- P599/Parameter P517 Ausb lendbereich 1 @ 0\mod_1328 092662665_388.doc x @ 11272 @ @ 1
P517
Skip freq. area 1
(Skip frequency area 1)
S P
0.0 ... 50.0 Hz
{ 2.0 }
Skip range for the >Skip frequency 1< P516. This frequency value is added
and subtracted from
the skip frequency.
Skip frequency range 1: P516 - P517 ... P516 + P517
Pos: 324 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P500- P599/Parameter P518 Ausb lendfrequenz 2 @ 0\mod_132 8092706493_388.doc x @ 11295 @ @ 1
P518
Skip frequency 2
(Skip frequency 2)
S P
0.0 ... 400.0 Hz
{ 0.0 }
The output frequency around the set frequency value (P519) is skipped.
This range is transmitted with the set brake and
acceleration ramp; it cannot be continuously
supplied to the output. Frequencies below the absolute minimum frequency should not be set.
0 = Skip frequency inactive
Pos: 325 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P500- P599/Parameter P519 Ausb lendbereich 2 @ 0\mod_1328 092748353_388.doc x @ 11318 @ @ 1
P519
Skip freq. area 2
(Skip frequency area 2)
S P
0.0 ... 50.0 Hz
{ 2.0 }
Skip range for the >Skip frequency 2< P518.
This frequency value is added and subtracted from
the skip frequency.
Skip frequency range 2: P518 - P519 ... P518 + P519
Pos: 326 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P500- P599/Parameter P520 Fang schaltung @ 0\mod_132809279 0587_388.docx @ 11341 @ @ 1