SK 54xEUsers Manual for Frequency Inverters
148 BU 0505 EN-3021
P541
Set digital outputs
(Set relays and digital outputs)
S
Pos: 350 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P500- P599/Parameter P541 Rel ais und digitale Ausgänge se tzen - Beschreibung [ SK 5xxE] @ 0\mod_13280938894 00_388.docx @ 11755 @ @ 1
0000 ... 3FFF(hex)
{ 0000 }
This function provides the opportunity to control the relay and the digital outputs independently of
the frequency inverter status. To do this, the relevant output must be set to the function "
value of
P541".
This function can either be used manually or in combination with a bus control.
Bit 0 = Output 1 (K1)
Bit 1 = Output 2 (K2)
Bit 2 = Output 3 (DOUT1)
Bit 3 = Output 4 (DOUT2)
Bit 4 = Dig. AOut 1
(Analog output 1)
Bit 5 = Output 5 (DOUT3)
(SK 540E and above)
Bit 6 = reserved
Bit 7 = reserved
Bit 8 = BusIO Out Bit 0
Bit 9 = BusIO Out Bit 1
Bit 10 = BusIO Out Bit 2
Bit 11 = BusIO Out Bit 3
Bit 12 = BusIO Out Bit 4
Bit 13 = BusIO Out Bit 5
Bits 13-12 Bits 11-8 Bits 7-4 Bits 3-0
Min. value
00
0
0000
0
0000
0
0000
0
Binary
hex
Max. value
11
3
1111
F
1111
F
1111
F
Binary
hex
BUS:
The corresponding hex value is written into the parameter, thereby setting the
relay and digital outputs.
ControlBox: The hexadecimal code is entered directly when the ControlBox is used.
ParameterBox: Each individual output can be separately called up in plain text and activated.
NOTE:
The setting is not saved in the EEPROM and is lost when the frequency
inverter is switched off!
Pos: 352 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P500- P599/Parameter P542 Ana logausgang setzen [SK 54 xE] @ 0\mod_1328094038778_ 388.docx @ 11801 @ @ 1
P542 [-01]
...
[-03]
Set analog output
(Set analog output)
S
0.0 ... 10.0 V
{ all 0.0 }
[-01] = Analog output: analog output integrated into the FI
[-02] = First IOE, "External analog output of first IOE": Analog output of the first IO extension
(SK xU4-IOE)
[-03] = Second IOE, "External analog output of second IOE": Analog output of the second IO
extension (SK xU4-IOE)
This function enables the setting of the analog outputs of the FI or the connected IO extension
module (SK xU4) regardless of their actual operating statuses. To do this, the relevant output
must be set to the function "External control" (e.g.: P418 = 7).
This function can either be used manually or in combination with a bus control. The value set here
will, once confirmed, be produced at the analog output.
NOTE: The setting is not saved in the EEP
ROM and is lost when the frequency inverter is
switched off!