EasyManua.ls Logo

nord NORDAC PRO SK 511E Series - Page 156

nord NORDAC PRO SK 511E Series
218 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SK 54xEUsers Manual for Frequency Inverters
156 BU 0505 EN-3021
P708
State of digital in.
(Status of digital inputs)
000000000 ...
111111111 (binary)
(Display with *SK-TU3-
PAR)
or
0000 ... 01FF (hex)
(Display with *SK-TU3-
CTR *SK-CSX-0)
Displays the status of the digital inputs in binary/hexadecimal code. This display can be used to
check the input signals.
Bit 0 = Digital input 1
Bit 1 = Digital input 2
Bit 2 = Digital input 3
Bit 3 = Digital input 4
Bit 4 = Digital input 5
Bit 5 = Digital input 6 (SK 520E and
above)
Bit 6 = Digital input 7 (SK 520E and
above)
Bit 7 = Analog input 1 (digital function)
Bit 8 = Analog input 2 (digital function)
Bit 9 = Digital input 8 (SK 540E and above)
Bit 10 = Digital input 1/1 IOE (SK 540E and above)
Bit 11 = Digital input 2/1 IOE (SK 540E and above)
Bit 12 = Digital input 3/1 IOE (SK 540E and above)
Bit 13 = Digital input 4/1 IOE (SK 540E and above)
Bit 14 = Digital input 1/2 IOE (SK 540E and above)
Bit 15 = Digital input 2/2 IOE (SK 540E and above)
Bits 11-8 Bits 7-4 Bits 3-0
Minimum value
0000
0
0000
0
0000
0
Binary
hex
Maximum value
0001
1
1111
F
1111
F
Binary
hex
ControlBox: the binary Bits are converted into a hexadecimal value and displayed.
ParameterBox: the Bits are displayed increasing from right to left (binary).
Pos: 387 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P700- P799/Parameter P709 Spann ung Analogeingänge [SK 54 xE] @ 0\mod_1328172336181_ 388.docx @ 12548 @ @ 1
P709 [-01]
...
[-10]
Analog input voltage
(Voltage of analog inputs)
-10.00 ... 10.00 V Displays the measured analog input value.
[-01] = Analog input 1: analog input 1, integrated into the FI
[-02] = Analog input 2: analog input 2, integrated into the FI
[-03] = External analog input 1, "External analog input 1": Analog input 1 of the first IO extension
[-04] = External analog input 2, "External analog input 2": Analog input 2 of the first IO
extension
[-05] = External Analog input 1, 2nd IOE, "External analog input 1 of the 2nd IOE": Analog input
1 of the second IO extension
[-06] = External Analog input 2, 2nd IOE, "External analog input 2 of the 2nd IOE": Analog input
2 of the second IO extension
[-07] = Analog function, Dig2, "Analog function of digital input 2": Analog function of digital input
2 integrated into the FI.
[-08] = Analog function, Dig3, "Analog function of digital input 3": Analog function of digital input
3 integrated into the FI.
[-09] = Encoder track A: Monitoring of the input signal of track A of an incremental encoder
(Terminal X6:51/52)
[-10] = Encoder track B Monitoring of the input signal of track B of an incremental encoder
(Terminal X6:53/54)
NOTE:
The voltage difference between tracks A and B of and incremental encoder can be
measured with the aid of parameter P709 [-09] and [-
10]. If the incremental encoder is
rotated the value of both tracks must jump between -
0.8V and 0.8V. For Hiperface
encoders the voltage ranges from -0.5V...0.5V. If the voltage only jumps between 0 and
0.8V the relevant rack is faulty.
It may be possible to determine the position with the
incremental encoder, but the interface is considerably more susceptible to faults. We
recommend replacement of the encoder!
Pos: 389 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P700- P799/Parameter P710 Spann ung Analogausgänge [S K 54xE] @ 0\mod_1328172483998_3 88.docx @ 12594 @ @ 1