BU 0505 EN-3021 157
P710 [-01]
...
[-03]
Analog output voltage
(Analog output voltage)
0.0 ... 10.0 V Displays the value which is output from the analog output.
[-01] = Analog output: analog output integrated into the FI
[-02] = First IOE, "External analog output of first IOE": Analog output 1 of the first IO extension
[-03] = Second IOE, "External analog output of second IOE": Analog output 1 of the second IO
extension
Pos: 390 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P700- P799/Parameter P711 Zus tand Digitale Ausgäng e @ 0\mod_1328172550774_388. docx @ 12617 @ @ 1
P711
State of relays
(State of digital outputs)
000000000 ...
111111111 (binary)
(Display with
*SK-TU3-PAR)
or
0000 ... 01FF (hex)
(Display with
*SK-TU3-CTR
*SK-CSX-0)
Displays the actual status of the signal relays.
Bit 0 = Relay 1
Bit 1 = Relay 2
Bit 2 = Digital output 1
Bit 3 = Digital output 2
Bit 4 = Dig. Fct. Aout 1 (digital function
Analog output 1)
Bit 5 = Digital output 3 (SK 540E and above)
Bit 6 = Digital output 1/1 IOE (SK 540E and above)
Bit 7 = Digital output 2/1 IOE (SK 540E and above)
Bit 8 = Digital output 1/2 IOE (SK 540E and above)
Bit 9 = Digital output 2/2 IOE (SK 540E and above)
Pos: 392 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P700- P799/Parameter P714 Betri ebsdauer @ 0\mod_132817 2684685_388.docx @ 1266 3 @ @ 1
P714
Operating time
(Operating time)
0.10 ... ___ h This parameter shows the time for which the FI was connected to the mai
ns and was ready for
operation.
Pos: 393 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P700- P799/Parameter P715 Fr eigabedauer @ 0\mod_13281727 31474_388.doc x @ 12686 @ @ 1
P715
Running time
(Enablement time)
0.00 ... ___ h This parameter shows the time for which the FI was enabled and supplied current to the output.
Pos: 394 /Anleitun gen/Elektronik/F U und Starter/5. Parameter /Parameterauflis tung (P000 ...)/ P700-P799/Parameter P716 Akt uelle Frequenz @ 0\mod_132 8172775215_388.doc x @ 12709 @ @ 1
P716
Current frequency
(Actual frequency)
-400.0 ... 400.0 Hz Displays the actual output frequency.
Pos: 395 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P700- P799/Parameter P717 Akt uelle Drehzahl @ 0\mod_13281728 89966_388.doc x @ 12732 @ @ 1
P717
Current speed
(Actual rotation speed)
-9999 ... 9999 rpm Display the actual motor speed calculated by the FI.
Pos: 396 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P700-P799/Parameter P718 Aktuelle Sol lfrequenz @ 0\mod_1328172 931732_388.doc x @ 12755 @ @ 1
P718 [-01]
...
[-03]
Present Actual setpoint
frequency
(Actual setpoint frequency)
-400.0 ... 400.0 Hz
Displays the frequency specified by the setpoint
(please see chapter 8.1 "Setpoint processing").
[-01] = Actual setpoint frequency from the setpoint source
[-02] = Actual setpoint frequency after processing in the FI status machine
[-03] = Actual setpoint frequency after frequency ramp
Pos: 397 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P700- P799/Parameter P719 Akt ueller Strom @ 0\mod_132817 2979998_388.docx @ 12778 @ @ 1
P719
Actual current
(Actual current)
0.0 ... 999.9 A Displays the actual output current.
Pos: 398 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P700- P799/Parameter P720 Akt ueller Momentstro m @ 0\mod_1328173025780_388.doc x @ 12801 @ @ 1