EasyManuals Logo

Notifier AIM-200 User Manual

Notifier AIM-200
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #12 background imageLoading...
Page #12 background image
12
Document 15949 Rev. E 4/12/95 P/N 15949:E
Table 3-1: Communications Loop Performance
Fault Condition
Single
Open on
Loop
Single
Ground
on Loop
Loop has
Been
Shorted
Loop
Shorted
and
Opened
Loop
Shorted
and
Grounded
Loop
Opened
and
Grounded
Commun
Loss
with
Control
Panel
Non-Redundant (2-Wire) Loop Operation
Trouble
(Note 1)
Trouble
with
Alarm
Capability
(Note 2)
Trouble Trouble Trouble Trouble Trouble
Redundant (4-Wire) Loop Operation
Trouble
with
Alarm
Capability
Trouble
with
Alarm
Capability
Trouble Trouble Trouble Trouble
with Alarm
Capability
Trouble
Isolated Redundant (4-Wire) Loop Operation (Note 3)
Trouble
with
Alarm
Capability
Trouble
with
Alarm
Capability
Trouble
with
Alarm
Capability
Trouble Trouble
with Alarm
Capability
Trouble
with Alarm
Capability
Trouble
Notes:
1. Trouble indicates that a trouble signal will be generated at the control
panel under the abnormal condition.
2. Alarm capability indicates whether or not an alarm signal can be trans-
mitted to the control panel during the abnormal condition.
3. Isolated redundant loop operation is a method of protecting, or isolat-
ing, entire physical zones of devices on the communications loop from
faults that occur within other areas of the loop.
Technical Manuals Online! - http://www.tech-man.com

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier AIM-200 and is the answer not in the manual?

Notifier AIM-200 Specifications

General IconGeneral
BrandNotifier
ModelAIM-200
CategoryI/O Systems
LanguageEnglish

Related product manuals