Document 15949 Rev. E 4/12/95 P/N 15949:E
BX-501 Base
These intelligent, addressable detectors provide analog information to
the AIM-200. The AIM-200 processes this analog information and con-
tinually makes decisions on the alarm, maintenance, or normal status of
each device. Each detector head mounts to a BX-501 base for ease of
installation or replacement. The sensitivity of each detector can be set by
the programmer at the AIM-200 for one of three levels (low, medium, and
high). Each detector responds to an address that is set in the head via
built-in rotary decimal switches.
BX-501BH Sounder built into base
B501 Flangeless base
SDX-551
An intelligent photoelectric smoke detector that provides analog mea-
surements of the optical smoke level in its chamber to the AIM-200 panel.
SDX-751
A low profile intelligent photoelectric smoke detector.
CPX-551
An intelligent ionization smoke detector that measures the level of com-
bustion products in its chamber using the ionization principle and reports
this measurement to the AIM-200.
CPX-751
A low profile intelligent ionization smoke detector.
FDX-551
An intelligent thermal sensor (135-degree F fixed temperature).
RA400Z
A remote single LED annunciator that can be wired directly off of an ad-
dressable detector for annunciation of that detector’s alarm status.
BX-501 Base
2.1 Optional Peripherals: Intelligent Detectors
Technical Manuals Online! - http://www.tech-man.com