Section One: The AIM-200
1.1 General Description
Note: AIM-200 features discussed in this document are available with AIM-200 software
part number 73264 or greater.
The Addressable Intelligent Module (AIM-200) functions as an interface between the Sys-
tem 5000 Fire Alarm Control Panel and intelligent/addressable devices. To the System
5000, the AIM-200 looks like an IZM-8 Initiating Zone Module. On its single communications
loop, the AIM-200 will communicate with up to 99 addressable modules and 99 intelligent
detectors. The AIM-200 will communicate with the following:
SDX-551 Intelligent Photoelectric Smoke Detector
SDX-751 Low Profile Intelligent Photoelectric Smoke Detector
CPX-551 Intelligent Ionization Smoke Detector
CPX-751 Low Profile Intelligent Ionization Smoke Detector
FDX-551 Intelligent Thermal Sensor
MMX-1 Addressable Monitor Module
MMX-2 Addressable Monitor Module
MMX-101 Miniature Monitor Module
CMX-2 Addressable Control Module
BGX-101L Addressable Manual Pull Station
DHX-501/DHX-502 Intelligent Duct Detector Housing (for use with SDX-551 only)
The 198 devices are mapped into eight software zones by the AIM-200. The status of these
zones is reported to the CPU-5000. The AIM-200 includes a digital display for identifying
the exact device address within a zone. The display is also used to display device types and
analog detector sensitivity values.
Although the AIM-200 is intended primarily as an initiating input module, it can support
CMX-2 Control Modules on the loop. The CMX-2 modules may be mapped to AIM-200
zones much like outputs are mapped to inputs during standard System 5000 programming.
The AIM-200 may be mixed in a system with any of these system modules:
IZM-8 Initiating Zone Module
IZE-A Initiating Zone Expander
ICM-4 Indicating Circuit Module
ICE-4 Initiating Circuit Expander
CRM-4 Control Relay Module
CRE-4 Control Relay Expander
VCM-4 Voice Control Module
VCE-4 Voice Control Expander
DCM-4 Dual Channel Module
TCM-2 Time Control Module (Single hazard release)
TCM-4 Time Control Module (Multiple hazard release)
In addition, ACM remote annunciators, AMG-1 and FFT-7 voice/telephone modules, and
several power supplies can be employed with an AIM-200.
Up to ten AIM-200s may be installed in one System 5000 for a capacity of 1,980 points
(subject to limitations of system power supply, refer to Appendix B).