EasyManua.ls Logo

Notifier AIM-200 - AIM-200 Control Module: Control-by-Detector

Notifier AIM-200
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
51
Document 15949 Rev. E 4/12/95 P/N 15949:E
Control-by-Detector
-
Control-by-Detector is a useful function for activating sounders in
the same room or location as the alarmed intelligent detector. To set up Control-by-Detector,
set detector address in the range 80-99. Ensure that a CMX-2 module exists with the same
address as the detector, and that the CMX-2 has not been mapped to any zones.
Alarm
From
Detector
Address
CMX-2
Address
CMX-2 Mapped
to Zone(s)?
Results
Detector 80-99 Same as
detector
No CMX will be activated if it shares the
address of the alarmed device and is not
mapped to any zone.
General CMX-2 Trouble
-
CMX-2 modules programmed for General Alarm,
Control-by-Module, or Control-by-Detector do not have a zone assignment. If a trouble
occurs on one of these devices, it is reported as trouble on Zone 1.
Non-Silenceable Notification Appliance Circuit
-
An CMX-2 configured as a Notification
Appliance Circuit (tabs intact) can be programmed in AIM-200 memory as a Form-C mod-
ule. The module will still function as a supervised notification appliance circuit, but will be
non-silenceable. This feature is suitable in applications that require strobe lights to continue
flashing after the signals have been silenced during an alarm.
Non-Silenceable Form-C Relays
-
A CMX-2 configured as a Form-C Relay (type CO)
cannot be silenced by the SIGNAL SILENCE switch on the CPU. These modules, regard-
less of their mapping assignments, can only be silenced by the RESET switch on the CPU.
Supervisory Zones
-
This supervisory monitoring function (tamper valves, etc.) is trans-
parent to the AIM-200. This programming selection is performed at the CPU.
Alarm Verification - The AIM-200 performs alarm verification if this feature is programmed
at the CPU. Verification delays are performed for alarms from detectors only.
Waterflow Zones - This System 5000 function (non-silenceable alarm) is transparent to
the AIM-200. If used, the installer should assign only flow switches to the zone.
Walk Test - The AIM module will perform a single-person test of all devices as follows:
1)Disable all eight AIM-200 zones using the DISABLE/ENABLE control on the CPU.
2)Disable all CMX-2 modules on the AIM-200 by entering Program Edit mode and
selecting the Cd code for each module. Remove the programming key.
3)Reset the system. (The remainder of the system, including other AIM-200s, contin-
ues to provide fire protection.)
4)Activate (alarm) each initiating device on the AIM-200.
5)Return to the panel and verify that the AIM-200 2 digit display is stepping through all
devices that were alarmed.
6)Reset the system and enable all eight AIM-200 zones.
7)Enable all CMX-2 modules on the AIM-200. Be sure to select the proper type.
8)Reset the system.
Technical Manuals Online! - http://www.tech-man.com

Related product manuals