EasyManua.ls Logo

Notifier AIM-200 - The MMX-2

Notifier AIM-200
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
22
Document 15949 Rev. E 4/12/95 P/N 15949:E
3.5 The MMX-2 Monitor Module
The MMX-2 monitor module is an addressable module that monitors conventional two-wire
smoke detectors. The supervised MMX-2 circuit can be wired as an NFPA Style B or Style
D initiating device circuit. Refer to the Device Compatibility Document for the type and
number of detectors the MMX-2 will support. Refer to Figures 3-13B and 3-14B for
MMX-2 wiring diagrams.
Communications Loop Connections
Connect the communications loop to MMX-2 Terminals 1(-) and 2 (+). The MMX-2 occupies
one module address on the loop. Set the rotary switches on the MMX-2 to the particular
loop address required.
NFPA Style B Initiating Device Circuit
Connect the alarm initiating devices to a single two-wire circuit. This circuit cannot be T-tapped
or branched in any fashion, and must be terminated across the last device by a listed 3.9K
ELR. Connect the circuit to MMX-2 Terminals 6 (-) and 7 (+). The maximum initiating device
circuit resistance is 25 ohms.
NFPA Style D Initiating Device Circuit
Connect the alarm initiating devices to a single four-wire circuit. This circuit cannot be
T-tapped or branched in any fashion. No external ELR is required for Style D wiring. Con-
nect the four-wire circuit to MMX-2 Terminals 6 (-) and 9 (-), then 7 (+) and 8 (+). The
maximum initiating device circuit resistance is 25 ohms.
Power
The MMX-2 requires connection of 24 VDC filtered, power limited, regulated and resettable
power on terminals 3 (-) and 4(+). Maximum stand-by current for two-wire detectors is
2.4mA. Maximum alarm current is 90mA.
Technical Manuals Online! - http://www.tech-man.com

Related product manuals