FC-2000 Controller Enclosure
Shield
To
AIM-200
Shield
Must employ metal conduit and
a metal box.
Figure 3-11: Shield Termination in Partial Conduit
Do not allow the shield drain wire to enter the control panel cabinet or the conduit. Connect
the drain wire to the termination point of the conduit run (such as a single-gang box as
illustrated above).
The conduit cannot be longer than 20 feet.