EasyManuals Logo

Notifier AIM-200 User Manual

Notifier AIM-200
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #25 background imageLoading...
Page #25 background image
25
Document 15949 Rev. E 4/12/95 P/N 15949:E
Figure 3-13B: NFPA Style B Initiating Device Circuit
Listed End-of-Line
Resistor
3.9K
24 VDC Two-Wire
Smoke Detectors
Refer to the MMX-2 Installation
Instructions, Document M500-03-00,
for more details.
AIM-200
MMX-2
24 VDC filtered,
regulated,
ressettable
power
1
2
3
4
9
8
7
6
5
-
+
+
-
-
+
-
+
To next device
on loop
+ -
+ -
MPS-24A, TB3 Terminals 2 (-) and 1 (+)
or
MPS-24B, TB2 Terminals 2 (-) and 1 (+)
or
UL-listed 24VDC power limited,
resettable, power supply for Fire
Protective Signaling
Technical Manuals Online! - http://www.tech-man.com