Programming Switches
Accepting or Rejecting Devices
The ENTER and SKIP LEDs will flash while the AIM-200 is in Auto-Program or Program Edit
mode.
Auto-Program
To accept a new device, press the ENTER switch. To reject a device, press the SKIP switch.
In either case, the AIM-200 will advance to the next address.
Program Edit
To store newly edited information on the device displayed, press the ENTER switch. To
leave device unchanged, press the SKIP switch. In either case, the AIM-200 will advance to
the next address.
Note: Holding in the SKIP switch will cause the AIM-200 to advance through successive
addresses quickly (10 per second).
Style 6 Loop Operation
This LED indicates that the AIM-200 has been programmed for redundant communications
loop operation. Select or deselect for the entire loop by pressing the control switch.
Note 1: To function as a redundant communications loop, the AIM-200 loop must be wired in
accordance with Figure 3-7.
Note 2: An isolated-redundant circuit is a variation of a redundant circuit (see Figure 3-8). If
wired as an isolated-redundant communications loop, the AIM-200 should be pro-
grammed for redundant circuit operation.
Technical Manuals Online! - http://www.tech-man.com

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier AIM-200 and is the answer not in the manual?

Notifier AIM-200 Specifications

General IconGeneral
BrandNotifier
ModelAIM-200
CategoryI/O Systems
LanguageEnglish

Related product manuals