L. Initial Start-up
L.1 Once all items in Section "K. Installation
Overview" have
been
verified. Turn on the 12 volt master switch.
L.2 Locate the Start/Stop switch at the Control Panel located on the
Generator inside
the
Service
Access
Door.
See
Exhibit
3.
Prime Generator Fuel Connections by depressing
Stop/Prime
button
for
ten
(10) seconds.
(11) Then,
depress
and release
the
Start
button,
to start
the
Generator.
(12) If Generator cranks but does not Start, repeat the Priming process, if
Generator still does not start, refer to section "M. Troubleshooting."
(13) 3 Upon starting the Generator, immediately inspect all fuel and
electrical connections for possible leaks (or pooling) of fuel or exhaust and/or
sparks or other electrical hazards:
Listen for excessive or irregular vibrations or rattling noises.
If any of the above items are heard or found shut-off the Generator
immediately, resolve the concern, re-start and verify concern is resolved while
the Generator is running.
If no concerns are found, verify 120Volt power is operational in the RV (a simple
way to do this is to view the microwave inside the RV and see if the display is
illuminated).
If 120Volt power is operational, run Generator for a minimum of five (5) minutes
before adding load such as the microwave or the air conditioners, allowing the
Generator to properly warm-up and break-in.
After five (5) minutes of smooth operation, and load has been applied, verifying
proper operation shut off the Generator, and proceed with verification of the other
start options.
(14) 4 Start Generator from inside the RV.
Depress the Start Switch inside the RV at the Remote Start Panel to verify the
Generator connected correctly and is operating properly.
(15) 5 Upon starting the Generator, immediately inspect all fuel and electrical
connections for possible leaks (or pooling) of fuel or exhaust and/or sparks or
other electrical hazards:
Listen for excessive or irregular vibrations or rattling noises.
If any of the above items are heard or found shut-off the Generator
immediately, resolve the concern, re-start and verify concern is resolved while the
Generator is running.
If no concerns are found, shut down the Generator.
Page 47 of 55 Rev. 1