5 CiA402 Drive Profile
5 - 24
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
This object sets the deceleration time.
To read the Speed (6049 to 01 hex), read the inverter parameter A004: Maximum Frequency.
To read and write the Time (6049 to 02 hex), read and write the inverter parameter F003:
Deceleration Time Setting.
This object sets the behavior during Shutdown (Operation enable Ready to switch on) .
Explanation of set values
This object sets the behavior during Disable operation (Operation enable Switched on).
Explanation of set values
This object sets the behavior when an error occurs.
Explanation of set values
6049 hex vl velocity deceleration
Sub-index 0: Number of entries
Setting range: Unit: Command
unit
Default setting: 02 hex
Size: 1 byte (U8) Access: RO PDO map: Not possible
Sub-index 1: Delta speed
Setting range: 00000000 to FFFFFFFF hex Unit: rpm Default setting: 00000708 hex
Size: 4 bytes (U32) Access: RO PDO map: Not possible
Sub-index 2: Delta time
Setting range: 0000 to FFFF hex Unit: s Default setting: 000A hex
Size: 2 bytes (U16) Access: RW PDO map: Not possible
605B hex Shutdown option code
Setting range: 1 Unit: Default setting: 1
Size: 2 bytes (Int16) Access: RW PDO map: Not possible
Set value Stop method
1 Deceleration stop
605C hex Disable operation option code
Setting range: 1 Unit: Default setting: 1
Size: 2 bytes (Int16) Access: RW PDO map: Not possible
Set value Stop method
1 Deceleration stop
605E hex Fault reaction option code
Setting range 1: Unit: Default setting: 1
Size: 2 bytes (Int16) Access: RW PDO map: Not possible
Set value Stop method
1 Deceleration stop