2 - 19
2 Starting a Sample System
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
2-6 SYSDRIVE MX2 Series Settings
2
2-6-1 RUN Command Setting
2-6 SYSDRIVE MX2 Series Settings
To perform control from the Communication Unit, the parameter settings must be changed from the
front panel digital operator of the inverter.
In this procedure, the inverter power supply must be turned ON. When the power supply is turned ON,
the inverter may operate in unintended way. Check the condition of the wiring and system carefully
before starting the procedure.
Refer to the User Manual (Cat No.I570) for the SYSDRIVE MX2-series inverter for details on operating
the inverter parameter settings and for the meaning of the parameter values.
Change the control method for the RUN command.
Change the control method for the frequency reference.
Set the operation of the reset signal.
* If parameter C102 is not displayed, first set parameter b037 to 01.
2-6-1 RUN Command Setting
Parameter No. Function name Data Default value
A002 RUN Command Selection 1 04 (Optional boad) 02 (Digital Operator)
2-6-2 Frequency Reference Setting
Parameter No. Function name Data Default value
A001 Frequency Reference Selection 1 04 (Optional boad) 02 (Digital Operator)
2-6-3 Reset Selection Setting
Parameter No. Function name Data Default value
C102 Reset Selection 03 (Trip reset only) 00 (Trip reset at power-ON)