Appendices
A-18
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
3012
hex
D5
hex
12B0
hex
Operation Frequency
Selection 2
A142 RW 00: Digital Operator
01: Volume
02: Voltage (FV) input
03: Current (FI) input
04: Modbus communication
(Modbus-RTU)
05: Do not set.
07: Pulse train frequency
Possible
(TxPDO)
3012
hex
D6
hex
12B1
hex
Operation Function
Operator Selection
A143 RW 00: Addition (A141 + A142)
01: Subtraction (A141 A142)
02: Multiplication (A141 A142)
Possible
(TxPDO)
4012
hex
D8
hex
12B3
hex
Frequency Addition
Amount Setting
A145 RW 0 to 40000 (100000) 0.01 [Hz] Possible
(TxPDO)
3012
hex
DA
hex
12B5
hex
Frequency Addition
Sign Selection
A146 RW 00: Frequency reference + A145
01: Frequency reference A145
Possible
(TxPDO)
3012
hex
DE
hex
12B9
hex
EL-S Shape
Acceleration
Curve Ratio 1
A150 RW 0 to 50 1 [%] Possible
(TxPDO)
3012
hex
DF
hex
12BA
hex
EL-S Shape
Acceleration
Curve Ratio 2
A151 RW 0 to 50 1 [%] Possible
(TxPDO)
3012
hex
E0
hex
12BB
hex
EL-S Shape
Deceleration
Curve Ratio 1
A152 RW 0 to 50 1 [%] Possible
(TxPDO)
3012
hex
E1
hex
12BC
hex
EL-S Shape
Deceleration
Cur
ve Ratio 2
A153 RW
0 to 50 1 [%] Possible
(TxPDO)
4012
hex
E2
hex
12BD
hex
Deceleration Stop
Frequency
A154 R/W 0 to 40000 (100000) 0.01 [Hz] Possible
(TxPDO)
3012
hex
E4
hex
12BF
hex
Deceleration Stop
Time
A155 RW 0 to 600 0.1 [s] Possible
(TxPDO)
4012
hex
E5
hex
12C0
hex
PID Sleep Function
Operation Level
A156 RW 0 to 40000 (100000) 0.01 [Hz] Possible
(TxPDO)
3012
hex
E7
hex
12C2
hex
PID Sleep Operation
Delay Time
A157 RW 0 to 255 0.1 [s] Possible
(TxPDO)
4012
hex
EB
hex
12C6
hex
VR Start Frequency A161 RW 0 to 40000 (100000) 0.01 [Hz] Possible
(TxPDO)
4012
hex
ED
hex
12C8
hex
VR End Frequency A162 RW 0 to 40000 (100000) 0.01 [Hz] Possible
(TxPDO)
3012
hex
EF
hex
12CA
hex
VR Start Ratio A163 RW 0 to VR End Ratio 1 [%] Possible
(TxPDO)
3012
hex
F0
hex
12CB
hex
VR End Ratio A164 RW VR Start Ratio to 100 1 [%] Possible
(TxPDO)
3012
hex
F1
hex
12CC
hex
VR Start Selection A165 RW 00: Start Frequency A161
01: 0 Hz
Possible
(TxPDO)
3013
hex
28
hex
1301 hex Retry Selection b001 RW 00: Trip
01: 0 Hz restart
02: Frequency matching restart
03: Trip after frequency matching
deceleration stop
04: Frequency pull-in restart
Possible
(TxPDO)
3013
hex
29
hex
1302 hex
Allowable Momentary
Power Interruption Time
b002 RW 3 to 250 0.1 [s] Possible
(TxPDO)
3013
hex
2A
hex
1303 hex Restart Standby Time b003 RW 3 to 1000 0.1 [s] Possible
(TxPDO)
3013
hex
2B
hex
1304 hex Momentary Power
Interruption/Undervolt
age Trip During Stop
Selection
b004 RW 00: Disabled
01: Enabled
02: Disabled during stop and
deceleration stop
Possible
(TxPDO)
3013
hex
2C
hex
1305 hex Restart During
Momentary Power
Interruption Selection
b005 RW 00: 16 times
01: No limit
Possible
(TxPDO)
4013
hex
2E
hex
1307 hex Frequency Matching
Lower Limit Frequency
Setting
b007 RW 0 to 40000 (100000) 0.01 [Hz] Possible
(TxPDO)
3013
hex
30
hex
1309 hex
Overvoltage/Overcurrent
Restart Selection
b008 RW 00: Trip
01: 0 Hz restart
02: Frequency matching restart
03: Trip after frequency matching
deceleration stop
04: Frequency pull-in restart
Possible
(TxPDO)
Index
Sub-
index
Register
No.
Function name
Parameter
No.
R/W Monitor and setting items
Data
resolution
PDO
map