3-45
3-7 Parameter List
3
Operation
Level and output terminal status
C055
Overtorque level
(Forward power
running)
0. to 200. (0.4 to 55 kW)
0. to 180. (75 to 132 kW)
100. No Yes %
4-97
C056
Overtorque level
(Reverse
regeneration)
100. No Yes %
C057
Overtorque level
(Reverse power
running)
100. No Yes %
C058
Overtorque level
(Forward
regeneration)
100. No Yes %
C061
Thermal warning
level
0. to 100. 80. No Yes % 4-47
C062 Alarm code selection
00: Disabled
01: 3-bit
02: 4-bit
00 No Yes 4-98
C063 0 Hz detection level
0.00 to 99.99
100.0
0.00 No Yes Hz 4-98
C064
Fin overheat warning
level
0. to 200. 120. No Yes °C 4-102
Parameter
No.
Function name Monitor or data range
Default
setting
Changes during
operation
Unit Page
Normal
b031 = 10
* 2nd/3rd control is displayed when "SET(08)/SET3(17)" is allocated to one of multi-function inputs from C001
to C008.