4-4SectionTypes of Commands and Responses
44
1-to-n Procedure
Command Format
@ Unit no M D L 1 X XXXXX FCS
∗
Header
00 to 07
Read/Write head word
(fixed to 1)
First address specification
Specifies a hexadecimal value (00
H
, 01
H
, 02
H
,..., FF-
H
) for the number of overwriting operations to be add-
ed.
Response Format
@ Unit no M D 7 5 FCS
∗
End code
75: The number of overwriting operations has not exceeded 100,000.
76: The number of overwriting operations has exceeded 100,000.
Header
00 to 07
4-4-12 Write Processing Repeat Command (RP)
Executes the processing the write command previously executed.
Command Format
RP CR
Header
∗
Terminator
Response Format
XX00 CR
∗
ASCII/HEX code specification
A: ASCII code, JIS 8 code
H: HEX code
R/W Head No. specification
(fixed to 1)
The write command information is cleared under the following conditions:
• When the Controller is power-reset.
• When a host communication error occurs during execution of write com-
mand
• If the repeat command is executed in this status, a command input error
occurs.