EasyManua.ls Logo

Osram BT Series - Page 37

Osram BT Series
58 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
OSRAM BT Control | Applications and settings
37
5.2.1.7 Standby level and time
When activated, the light will go to the standby level after
the switch-off delay time has expired. The light will switch
off after the standby time has expired.
Activate the standby level and time
1. Open the main menu.
2. Open “Current configuration”.
3. Open “Advanced settings”.
Activate standby level and define
the standby level and standby time
according to your needs.
5.2.1.8 PIR inhibit timer after manual switch-off
Change the PIR inhibit timer
1. Open the main menu.
2. Open “Current configuration”.
3. Open “Motion detection”.
Change the inhibit timer after
manual switch-off.
The timer starts when manually
switched off via pushbutton or app.
As long as the timer is active, the
presence sensor will not switch on the
light. Instead, it will retrigger the timer.
Change the setting to 01:00:00 to
be sure that the light will not switch
on automatically when you come
back.
Leave it at 00:00:30 sec if you want
the automatic switch-on to be active
again after you have left the room.
5.2.1.9 Manual setting of light regulation
Depending on the availability of natural daylight and the
room setup, the light regulation value might need to be set
manually – instead of automatically – to get the right
amount of light according to customer needs.
Manual setting of light regulation
1. Open the main menu.
2. Open “Current configuration”.
3. Now open the “Light regulation”.
4. Click on “Manual” to define the
required light level manually.
5. Dim the light to the required level
and use a lux meter to measure the
amount of light directly at the place
where the light is needed, e.g. a desk
surface.
6. Click on “Save” to store the
light level as a reference value for
light regulation.
3
3
4
5
6
2
1
3
2
1
2
1

Table of Contents