OSRAM BT Control | Applications and settings
38
5.2.1.10 State after power failure
“State after power failure” defines the behavior of the
connected DALI LED drivers after a power failure.
Change the state after power failure
1. Open the main menu.
2. Open “Current configuration”.
3. Open “Advanced settings”.
Change the state after power
failure between on/off/last state/
standby according to your needs.
5.2.2 Meeting room with scene control
5.2.2.1 Requirements
The meeting room luminaires can be switched and dimmed
and pre-configured. Light scenes can be recalled by using
pushbuttons.
The light will be switched on manually when a person en-
ters the room, but automatically turned off by the sensor
after a 15-minute delay time.
During presence, the daylight harvesting function will dim
the artificial light up and down according to the amount of
daylight available.