OSRAM BT Control | Applications and settings
45
Change of default setup for group 4
1. Open the main menu.
2. Open “Current configuration”.
3. Open “Push Button Setting” and
click on “Configure” for the “Push
Button Coupler”.
4. Please identify the dedicated PBC of
group 4 by pressing the connected
pushbutton.
5. Select the “4. DIM – 4 groups”
profile and click on “Done” to save
this change of configuration.
5.2.4 Corridor including standby (infinite timer)
5.2.4.1 Requirements
The lights will be switched on automatically when a person
enters the corridor and automatically dimmed down to a
light level of 10 % after the delay time has expired and if no
presence is detected.
The light will stay on and never switch off due to safety
requirements, so the standby time is infinite.
2
1
3
4
5