EasyManua.ls Logo

Pace PAI - Air Measuring Device Connections; Air Measuring at the Fan Inlets

Pace PAI
108 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SECTION 3 - HANDLING, STORAGE, AND INSTALLATIONPACE Installation & Assembly Manual
Issue Date: 07/03/2018
70
Form PA102.20-N1
AIR MEASURING DEVICE
CONNECTIONS
Air Measuring at the Fan Inlets
COMETER is a probe attached to the fan bearing
support on Comefri Forward Curve fans from size
7 x 7 up to 18 x 18. The probe is located on the
outboard side of the housed fan assembly. The
probe is piped to the negative (-) port of a factory
mounted transducer on the fan wall. The posi-
tive (+) port is left open to the fan section. Wiring
is not provided to the transducer unless factory
packaged controls were selected.
PIEZORING (PIEZOMETER) is a tting or series
of ttings in the inlet cone(s) of housed fans larger
than 18 x 18 and all sizes of Plenum fans that are
combined into a single connection piped to the
negative (-) port of a factory mounted transducer
on the fan wall. The positive (+) port is left open
to the fan section. Wiring is not provided to the
transducer unless factory packaged controls were
selected.
The fan manufacturer does not recom-
mend placement of the ow measuring
probes inside the fan inlet cone in the
path of airow. These devices create
disturbances and unpredictable perfor-
mance losses.
Figure 110 - High and Low Connections for an in Fan
Air Monitoring System
LD17231
Figure 111 - High and Low Connections and
Associated Tubing for Fan Mounted Air Monitoring
System
LD17232
Figure 112 - Port Locations for Fan Mounted Air
Monitoring System
LD17233
High Port
Low Port
Air Measuring at Unit Outside Air Inlets
AMS-60 used on Indoor air handlers usually mea-
sure outside air. This can be provided with one
or two pairs of positive (+ or High) and negative
(- or Low) pressure tube connections. Connect
(+) & (-) respectively to the (+) & (-) ports of the
transducer(s). Wiring & transducer are not pro-
vided unless factory packaged controls were se-
lected.

Table of Contents