105 
F96  Transistor module 
over-temperature 
protection 
Overheat is detected in the IPM to block the heat. The diagnosis code is stored in the 
memory and the compressor stops. The error code is displayed if this error is detected 
four times within 30 minutes. 
<Points of diagnosis> 
1.  Interrupted heat radiation on the outdoor unit and the failure of outdoor unit fan. (The 
outdoor unit fan does not rotate.) 
2.  Failure of IPM (outdoor unit control board). 
3.  Check for short-circuit and continuity of IPM sensor. 
  Interrupted heat 
radiation 
  Outdoor unit fan 
motor failure 
  Overload 
conditions 
F97  Compressor over-
temperature 
protection 
When the temperature of the compressor exceeds 103°C, the diagnosis code is stored 
in the memory and the compressor stops. It resumes operation after 180 seconds when 
the temperature is 92°C or below. The error code is displayed if this error is detected 
four times within 20 minutes. 
<Points of diagnosis> 
1.  Check of refrigerating cycle: Gas leak (Low refrigerant level). 
Symptom: The outdoor unit sometimes stops. 
2.  The compressor temperature sensor is checked when the error code is displayed 
and the compressor stops. (Check for change in characteristic and resistance value.) 
3.  Interrupted heat radiation on the outdoor unit and the failure of outdoor unit fan. (The 
unit fan does not rotate due to open state.) (The error is sometimes detected in case 
of overload. In this case, F97 remains in the memory.) 
  Low refrigerant 
level (relatively 
low) 
  Interrupted heat 
radiation 
  Overload 
conditions 
F98  Total current 
protection 
If the total current exceeds the preset value, this diagnosis code is stored in the memory 
and the compressor stops. It resumes operation after 180 seconds. The error code is 
displayed if this error is detected three times within 20 minutes. [Refer to “Total Current 
Protection Control” for the preset value] 
<Points of diagnosis> 
1.  AC voltage of the outdoor unit terminal board during operation: The voltage should 
drop by less than 5% from the voltage at the STOP state. (The rated voltage is to be 
±110% even during the operation.) If the voltage drops by not less than 5%, or in 
case of sudden change in voltage, check for the length/thinness of the indoor wiring 
and indoor/outdoor connection wire. 
2.  Check for the interrupted heat radiation on the outdoor unit (during cooling 
operation): The outdoor unit is usually not stopped and only subjected to the 
capacity restriction by way of current control. No diagnosis code is displayed. 
  High refrigerant 
level 
  Interrupted heat 
radiation 
F99  DC peak operation 
error 
When overcurrent, overheat or drop in supply voltage is detected in the IPM within 30 
seconds from the start of the compressor, the compressor stops and then resume 
operation in 60 seconds.  When the error is detected seven consecutive times, the 
compressor stops operation and the error code is displayed. 
<Points of diagnosis> 
1.  The compressor stops under F99 within 30 seconds from its start:  
When the lead wires are disconnected from U, V and W on the IPM then operate: 
  If F93 is displayed and the compressor stops: Check of refrigerating cycle, 3-
way valve opening failure, clogged pipe, failure of compressor (disconnection of 
coil). 
  If F99 is displayed and the compressor stops: Check for IPM power supply of 
DC15V (4 locations) and voltage of DC280V. Failure of outdoor unit control 
board. 
2.  If the compressor stops after it operates for more than 5 minutes, a failure of the 
power circuit and refrigerant cycle is also checked. 
  Compressor 
  Outdoor unit control 
board 
[Examples of the How to Identify the Faulty Point] 
The following is some flow charts which illustrate on how to identify the faulty point for each code (examples).