17.4.19 H97 (Outdoor Unit Fan Motor Lock Error)
Troubleshooting
Diagnosis Procedures and Cause
Measures to be Taken
Open-circuited or short-circuited
No abnormality is observed
No abnormality is observed
No abnormality is observed
The voltage is not present
When the power is supplied to the outdoor unit, check if DC5V is
present between
4
5
of the 5-pin connector.
(Measure the voltage after the fan motor connector is removed from
the board.)
Replace the outdoor unit fan motor.
Measure the coil resistance of No.3 pin of the fan motor.
Check if between
1
3
,
1
5
, and
3
5
of 3-pin and 5-pin
connector is not open-circuited or short-circuited.
When the outdoor unit is in operation, check if AC voltage is present
between
1
3
,
1
5
, and
3
5
of 3-pin and 5-pin connector.
The voltage is not present
Replace the outdoor unit control board.
No abnormality is observed
A foreign object is
stuck on the fan
Check if a foreign object is stuck on the fan.
For the type with two connectors (5-pin and 3-pin)
Fix the problem.
No abnormality is observed
Disconnection/Imperfect
connection of the connector
Check for bad connection of the fan motor connector.
Fix the problem.